A 1952 town hall, rebuilt in eight and a half months

Llinars del Vallès rebuilt its 1952 town hall in 8.5 months, co-funded by NextGenerationEU. Catalonia’s first EnerPHit certified office building.

A 1952 town hall, rebuilt in eight and a half months

In January 2024, Llinars del Vallès started work on its town hall with a deadline it could not move. The building on the Plaça de la Vila dated from 1952, around 955 m² over three floors, and it had the problems you would expect: solid walls with no insulation, original windows, and four separate citizen service desks spread through a plan that had grown by accretion. By 16 September the works had to be finished, or the European funding paying for three quarters of them would be lost.

It got finished. The building is now the first administrative building in Catalonia certified to the Passivhaus EnerPHit standard, in the Plus class.

Side by side comparison of the town hall facade before and after the retrofit
The same elevation before and after: bare masonry and original windows, then an insulated envelope.

A fixed budget and a fixed date

The works cost 804,650 € including VAT, about 842 € per square metre. Of that, 601,750 € came from the Recovery, Transformation and Resilience Plan, funded by the European Union through NextGenerationEU, and 202,900 € from the council’s own budget. The grant set both the ceiling and the calendar: four months to produce the design, eight and a half to build.

That matters more than it sounds. A deep energy retrofit is usually sold as something slow and disruptive. This one was programmed like any other municipal contract, in a building that stayed in use.

Wrapping a building that was never designed to be wrapped

The façades were insulated from the outside with Ytong Multipor mineral insulation board — 120 mm on the main brick elevations, 80 to 100 mm where the geometry was tighter — taking the walls from bare masonry to between 0.24 and 0.41 W/(m²K). The flat roofs received 80 mm of XPS over 40 mm already there; the pitched roofs 100 mm, giving 0.26 to 0.28 W/(m²K). A liquid applied membrane was taken around the whole envelope behind the insulation to form a continuous airtight layer.

Close up of mineral insulation board being fixed over a liquid applied membrane at the foot of a wall
Mineral insulation board going on over the continuous airtight membrane at the base of the wall.

Insulating from the outside rather than the inside was the decision that made the rest possible. It keeps the existing masonry inside the warm envelope, where its weight steadies the internal temperature through a Vallès summer. It leaves the junctions accessible, so they can be resolved rather than worked around. And it costs the council nothing in floor area, which in a building where four service desks were being consolidated into one mattered as much as the energy.

Every window was replaced with triple glazed, low-e, argon filled Smartwin timber-aluminium units made by Ventanas Gardea, installed at 1.27 W/(m²K) including frames and fixing. The insulation was returned into the reveals, so the frames sit within the insulation line rather than at the edge of it.

Diagram of the floor to wall junction showing continuous insulation and the calculated thermal bridge value
The slab-to-wall junction, with the insulation line carried through. Linear thermal bridge coefficient 0.096 W/(m·K).

The junctions decide the result

Insulation thickness is the easy part. What determines whether a retrofit performs is what happens where elements meet, and in a 1950s building those junctions were never detailed for it.

Two-dimensional thermal bridge calculations were made to ISO 10211 for the critical details. At the slab to wall junction the linear thermal bridge coefficient came out at 0.096 W/(m·K), with a temperature factor of 0.766 against a required minimum of 0.31 for this climate. The minimum internal surface temperature in that detail is 15.3 °C when it is freezing outside, which is what keeps condensation and mould off it.

Checked rather than assumed

A certified building is not one where the design intent was good. It is one where every number was traced back to something real before it was accepted.

The energy model is rebuilt against evidence: conductivity values taken from the data sheets for the boards actually delivered to site, window performance from the installed units including frames and fixings rather than the glass alone, heat recovery from the ventilation unit’s own component certificate rather than a brochure figure, areas checked against site photographs. Where a value cannot be evidenced, it does not go into the model.

Then the two things that cannot be modelled are measured. Airtightness is tested on the finished building, not declared. Ventilation flow rates are commissioned and measured room by room, because a heat recovery unit that is 84% efficient on paper recovers nothing useful if the system is unbalanced.

That is the difference between a building that should perform and one that does.

Every gap in the building, added up

On 15 October 2024 the completed building was tested with a blower door. Air is pushed in and drawn out at a range of pressures and the leakage is measured against the internal volume, here 2,346 m³, inside an envelope of 1,428 m².

The result was n50 = 0.88 air changes per hour, measured, against a limit of 1.04 for this project. That is 2,065 m³/h of air leaking at 50 pascals.

The number that makes it real is the equivalent leakage area. Add every crack, service penetration and badly closing joint in the building together and they come to 0.0629 m²: a single square hole about 25 cm by 25 cm, in a 1,428 m² envelope that was built in 1952.

Graph of the measured air change rate against the certification limit, with the equivalent leakage area shown to scale
The measured airtightness result against the limit, and the leakage area it represents.
Mechanical ventilation unit with large insulated ducts on a flat roof during installation
The ventilation unit and its ductwork being installed on the roof.
Office workspace with timber framed triple glazed windows and desks along a wall
An office on the upper floor: daylight, triple glazing and continuous filtered air.

Air, heat and cold

Ventilation is a Zehnder Carma unit on the roof, Passivhaus certified, recovering 84% of the heat from the air it extracts. It runs continuously and filters what it brings in, which in an office with a public counter is as much about air quality as about energy.

It was commissioned in March 2025 and measured room by room: 2,351 m³/h supplied against 2,330 designed, and 2,357 m³/h extracted. Balanced to within one percent of the design, which is where heat recovery either works or does not.

Heating comes from the municipal biomass district network through wall mounted fan coils. The same fan coils provide cooling in summer from a chiller on the roof. A Loxone system monitors energy use and indoor air quality in real time.

Solar, and what it covers

There is 19.3 kWp of photovoltaic on the roof: 13.6 kWp installed as part of the works, alongside 5.7 kWp already there. Together they produce about 25,300 kWh a year against a building demand of around 36,300 kWh, roughly 70% of everything the building uses, in final energy. In the certification’s terms, the building generates 67 kWh/(m²·a) per square metre of building footprint of renewable energy against a renewable primary energy demand of 43 kWh/(m²·a), per square metre of treated floor area, which is what earns the Plus class.

Photovoltaic panels mounted on the roof of the town hall
The photovoltaic array on the roof, 19.3 kWp in total.

What the certificate says

Measured against a treated floor area of 761 m², and against the EnerPHit criteria for this climate:

Heating demand came in at 18 kWh/(m²·a) against a limit of 20. Cooling and dehumidification at 4 against 15. Excessive humidity occurs 4% of the year against a limit of 10%. Airtightness, 0.88 against 1.04.

Not one of them is a near miss, and all of them are on a building from 1952.

Graph comparing the certified heating demand, cooling demand, humidity frequency and airtightness against their limits
The certified results against the EnerPHit criteria for this climate.
The town hall seen from the public square with trees and planters in front
The building back in use on the square it has stood on since 1952.

The point

A municipality with a capped budget and a hard deadline took a post-war office building and got a certified deep retrofit out of it in eight and a half months. The people working there have stable temperatures, filtered air and daylight; the council has an asset worth more and a running cost a fraction of what it was.

There are a great many town halls like this one.

Short version

1952 town hall, around 955 m², retrofitted in eight and a half months for 804,650 € with NextGenerationEU funding. 120 mm external mineral insulation, triple glazing, n50 = 0.88, 84% heat recovery, 19.3 kWp of solar. Heating demand 18 kWh/(m²·a). Catalonia’s first EnerPHit certified administrative building, Plus class.

Praxis Resilient Buildings carried out the Passivhaus certification and the airtightness testing on this project.

Project page: Ajuntament Llinars del Vallès, Catalonia, EnerPHit Plus retrofit

How to Renew Your Passivhaus Designer/Consultant or Tradesperson Certificate (2026 Guide)

How to renew your Passivhaus certificate as a Designer/Consultant or Tradesperson: both routes, 100/30 credit points, fees and the 2025 PHI changes.

How to Renew Your Passivhaus Designer/Consultant or Tradesperson Certificate (2026 Guide)

Passing the Certified Passivhaus Designer/Consultant or Tradesperson exam is a real achievement, but the certificate only lasts five years. If you need to renew your Passivhaus certificate, there is good news: the Passive House Institute (PHI) made renewal considerably easier in 2025. The catch is that much of the advice still online describes the old rules.

This guide explains how renewal works today for both qualifications. It is based on PHI’s current Regulations for Continuing Education, valid from 1 January 2025, and on PHI’s own renewal pages.

Title graphic for a guide to renewing Passivhaus Designer, Consultant and Tradesperson certificates, showing 5 years validity, 100 CP and 30 CP
Diagram of the two renewal routes for Passivhaus Designer/Consultant and Tradesperson certificates: project documentation or credit points

Passivhaus certificate renewal at a glance 

  • Both certificates are valid for five years and can be renewed as many times as you like.
  • Designers/Consultants renew with a certified building or 100 credit points (CP).
  • Tradespeople renew by documenting their own work or with 30 CP.
  • One CP equals one 45-minute learning unit.
  • You cannot renew by retaking the exam.
  • Praxis is an accredited assessing body for certificate renewals. Contact us here for a fee quote

How long is a Passivhaus certificate valid? 

Both certificates are valid for five years, and you can renew them as often as you like. If yours expires, your entry in PHI’s public directory of certified professionals is deactivated and deleted six months later. That listing matters: clients find you there, and some tenders ask for proof of a valid certificate.

You cannot renew by retaking the exam, even if your certificate expired long ago. The exam is only for your first qualification. After that, there are two ways to renew: by documenting real project work, or by collecting continuing education credit points.

How to renew as a Passivhaus Designer or Consultant 

Route 1: document a certified building 

You can renew by submitting documentation for a building where you were responsible for the energy-relevant design, including the PHPP. The building must:

  • be completed and in use;
  • be certified as a Passive House, EnerPHit retrofit or PHI Low Energy Building (EnerPHit pre-certification for a staged retrofit also counts);
  • be listed in the Passive House Database.

You can submit to a PHI-accredited assessing body such as Praxis, in English, Spanish, Catalan, French and German, plus a summary in English. You will need:

  • the application form;
  • a detailed building description using PHI’s template;
  • the unprotected PHPP file;
  • a copy of the building certificate;
  • the building’s database ID;
  • if you weren’t the lead designer, a signed statement from the designer confirming your role.

Normally only one person can use a given building. For complex buildings over 4,000 m², two people may each submit if they were responsible for different parts, such as the envelope and the building services.

Route 2: collect 100 Passive House credit points 

If you don’t have a certified building in the pipeline, you can renew with 100 CP. One CP equals one 45-minute learning unit, with a maximum of 8 CP per day. Courses and events must focus on highly energy-efficient construction and the Passivhaus Standard.

Comparison table of the old 2016 and current 2025 Passivhaus Designer/Consultant renewal rules

What changed in 2025 

If you last read up on renewal a few years ago, several important rules are different now:

  • You keep the Designer title. Renewing through credit points no longer downgrades a Designer to Consultant.
  • All your points can come from one source. The old caps on how many points could come from each category have been removed. Courses alone, events alone or teaching alone are all fine.
  • Teaching counts at the same rate as attending.
  • Extra points can be carried forward to your next renewal.
  • Expired certificates can still be renewed with points. All 100 CP must be less than five years old when you apply.

PHI’s Designer/Consultant certificate page sets out the current process in full.

How to renew as a Passivhaus Tradesperson 

Route 1: document your own work 

Tradespeople can renew by documenting their own work on a highly energy-efficient building. Unlike the Designer route, the building does not have to be a certified Passive House. Your work just has to meet the energy criteria for your trade and climate zone. The process has three steps:

  • Find your climate zone on PHI’s climate zone map.
  • Download the criteria for your trade. PHI publishes separate requirements for shell construction, carpentry, roofing and plastering insulation, window installation, ventilation, heating and hot water, and airtight electrical installations.
  • Submit the renewal application, your work documentation (using PHI’s template) and a short declaration from the client, designer or business owner confirming that you did the work yourself. These go to a PHI-accredited assessing body such as Praxis, with a summary in English.

Route 2: collect 30 credit points 

Alternatively, collect 30 CP. One 45-minute learning unit equals one CP, and you can earn no more than 20 CP in any one area (teaching, events or advanced training courses). Full details are on PHI’s Tradesperson certificate page.

How to log your Passive House credit points 

PHI now manages credit points online, and renewal is much easier if you log them as you go. PHI’s credit point FAQ shows the process with screenshots.

  • Step 1: Log in to your Passive House database account and open Exams & Certificates.
  • Step 2: Click Add accredited training, then search for the event by name or ID.
  • Step 3: Upload your proof of attendance and click Add to attended.
  • Step 4: PHI checks your proof before the points are credited.
  • Step 5: When you reach 100 CP (Designer/Consultant) or 30 CP (Tradesperson), the Renew certificate button becomes active.
  • Step 6: Click it. PHI sends an invoice, and once it’s paid, you receive your renewed certificate by email.
Six-step diagram showing how to log Passivhaus credit points and renew a certificate in the Passive House Institute online portal

How much does it cost to renew? 

Praxis is an accredited assessing body for certificate renewals, for Designers and Tradespersons looking to renew their certificates through project and work documentation. Contact us here for a fee quote.

A Praxis Resilient Buildings trainer presenting at a Passivhaus training session in Barcelona

Where to find Passivhaus credit points 

  • PHI’s directories of accredited events for Designers/Consultants and for Tradespeople. Every event has an ID number, and you’ll need it to claim.
  • Conferences give the most points in one go. The International Passive House Conference typically awards around 36 CP. National conferences such as the UK Passivhaus Conference and the AECB Conference typically award around 10–16 CP.
  • iPHA webinars are worth 2 CP each, including the recordings. The same material viewed on Passipedia doesn’t earn points.
  • Accredited training providers and national affiliates offer courses, masterclasses and webinars, many of them online. Our Passivhaus courses at Praxis Resilient Buildings are validated by PHI, and we also run in-company training for teams.
  • If a relevant event isn’t listed, ask the organiser to submit it to PHI using the event accreditation form. This can be done retrospectively.

Beware of outdated renewal advice 

Several guides still online describe the 2016 rules. Treat the following claims as out of date:

  • that no more than 70 of your 100 points can come from one category;
  • that points can’t be carried forward;
  • that Designers can only keep their title by documenting a building;

If in doubt, contact us here.

Five tips for a stress-free renewal 

  • Start straight after you qualify. Aiming for about 20 CP a year for Designers, or 6 CP a year for Tradespeople, keeps renewal stress-free.
  • Log every event as soon as you’ve attended it and keep your attendance certificates.
  • Check that an event is accredited, and note its ID, before you book.
  • Don’t let it lapse. Expired certificates can still be renewed, but you lose your directory listing and can’t use the seal in the meantime.
  • Keep it valid if you want add-on seals. Additional qualifications such as PHPP Expert, Retrofit or Construction Verifier require a valid main certificate.
Bar and line chart showing an example five-year plan to collect 100 Passivhaus credit points from webinars, online courses and conferences

Praxis Resilient Buildings is an engineering and consultancy practice in Barcelona, and an accredited Passivhaus training company recognised by the Passive House Institute and Plataforma PEP. This guide reflects PHI’s rules as of September 2026; always check the latest regulations with PHI before applying. Sources: Passive House Institute (certificate pages, FAQ, Regulations for Continuing Education 2025, fee schedules 2025), Coaction, The Passive House Network, Passivhaus Trust, Passive House Canada.

One Year in a Passivhaus Plus Home: 11,929 kWh Generated and €332 in Energy Bills 

First-year measured data from Can Naiades, a Passivhaus Plus home near Barcelona: 11,929 kWh generated, 85% self-sufficient, €332 of electricity bills.

One Year in a Passivhaus Plus Home: 11,929 kWh Generated and €332 in Energy Bills 

I’ve learnt that the first few months after moving into a house you have built yourself are probably more stressful than the whole construction process. There are bills still to pay and no money in the account. Your business has suffered because you gave so much of your time to the project. Aches and pains surface in odd parts of your body from too many hours hunched over a cost-control spreadsheet.

And then there is a point where you close the spreadsheet, decide never to open it again, and actually begin enjoying the wonders of living in a decent house — one that is genuinely comfortable, has great air quality, and is remarkably cheap to run.

That was a year ago. We now have twelve full months of measured data from Can Naiades, our certified Passivhaus Plus home in Sant Julià d’Alfou, 40 km north-east of Barcelona. This is what the first year in a Passivhaus Plus home actually looks like, in kilowatt hours and in euros.

Can Naiades, vivienda certificada Passivhaus Plus cerca de Barcelona, fotografiada al atardecer
Can Naiades at dusk. The house was certified Passivhaus Plus and Near Zero CO₂ in 2026. Photo: Pol Viladoms. 
Espacio de doble altura en Can Naiades con puertas correderas de triple vidrio orientadas al sur abiertas al jardín
The double-height living space opens onto the terrace. Solar gains through the south glazing cover 79% of the heating demand. 

A quick recap of the house 

Can Naiades is a two-storey, four-bedroom family home of 127 m² treated floor area, built on a prefabricated lightweight timber frame. The envelope is insulated with recycled glass wool — 250 mm in the walls and 350 mm in the roof — with triple-glazed timber-aluminium windows at Uw 0.81 W/(m²K) as installed, and an airtightness of 0.44 air changes per hour at 50 Pa. Every window has an external venetian blind. If you want the full build story, we set it out in the fifteen steps we took towards a comfortable, healthy, resilient and efficient home.

There is no conventional central heating system. A heat pump with a single ducted split unit, sized for the cooling load, also provides occasional heating; the rest is handled by small towel radiators in the bathrooms and an underfloor loop in the ground-floor bathroom. Fresh air comes from a balanced mechanical ventilation unit with heat and moisture recovery, running continuously. On the roof sit 21 photovoltaic panels totalling 8.5 kWp, paired with a 13.8 kWh battery.

Here is the finished house in a minute, before we get to the numbers.

How we calibrated the PHPP model 

Comparing measured data against a design model is only meaningful if the model has been told the truth about the year that actually happened. So before making any comparison, we calibrated the PHPP certification model in two ways.

First, we replaced the standard climate data set with outdoor air temperature and relative humidity recorded at a local meteorological station over the monitoring period. Second, we adjusted the occupancy assumptions to match the household as it really is — three adults and two young children — rather than the standard occupancy the certification method assumes.

That matters. Without those two corrections you are comparing a real house in a real year against a generic house in an average year, and any agreement — or disagreement — between the two tells you very little.

Bar chart comparing PHPP predicted and measured annual PV generation and energy consumption at Can Naiades
Annual PV generation and consumption, PHPP prediction against measured data, September 2025 to August 2026.

What the house generated, and what it used 

Over the twelve months from 1 September 2025 to 31 August 2026, the photovoltaic array generated 11,929 kWh. Total consumption across the same period was 7,835 kWh, of which 898 kWh went into charging a plug-in hybrid car — roughly 4,000 km of electric running. Strip the car out and the house itself used 6,937 kWh.

So the house generated 52% more electricity than everything in it consumed, car included. Against the building alone, generation was 72% higher than consumption.

The agreement with the calibrated model is the part we find most satisfying. PHPP predicted 11,139 kWh of generation; the array delivered 11,929 kWh, 7% ahead. PHPP predicted 7,052 kWh of household consumption; the meters recorded 6,937 kWh, 1.6% below. For a whole-building energy model to land within a couple of per cent of reality over a full year is about as good as this work gets.

Of the 11,929 kWh generated, 6,697 kWh was used directly in the house — a self-consumption rate of 56%, helped considerably by the battery. The remaining 4,964 kWh went to the grid. Over the year the house drew just 1,149 kWh back from the grid, which means 85% of everything it consumed was covered on site, and it exported 3,815 kWh more than it imported. Averaged out, that is 32.7 kWh generated and 21.5 kWh consumed per day, with only 3.1 kWh a day coming off the grid.

Consumption, month by month 

The annual totals agree almost exactly, but the monthly pattern varies. From December to May the house used more than the model predicted, most noticeably in January at around 30% above. From June to September the reverse held, with measured consumption comfortably below the model — particularly in July and August, where PHPP expected over a megawatt hour a month and the house used considerably less. Our first summer article covers how the house is kept cool: the blinds, natural night ventilation where possible, and a small amount of active cooling from the single split unit.

So PHPP overestimated our summer cooling energy and underestimated our winter and shoulder-season electricity use, and the two discrepancies very nearly cancel out across the year. That is consistent with the caveats in EN ISO 13790 — since superseded by EN ISO 52016 — on which PHPP’s monthly energy demand calculations are based: the monthly method is reliable for the annual total but not necessarily for individual months, and relative errors can be large at the start and end of the heating or cooling season.

Bar chart of monthly PHPP predicted versus measured energy consumption at Can Naiades
Monthly energy consumption, PHPP prediction against measured data, excluding car charging.
Bar chart of monthly PHPP predicted versus measured solar PV generation at Can Naiades
Monthly PV generation, PHPP prediction against measured output.

Solar generation, month by month 

The array beat the model in nine months out of twelve, with the largest gains in April and June. Three came in below prediction: January and December, both marginal, and September, where measured output of 650 kWh fell well short of the 990 kWh predicted. September stands out against every other month, explained by cloudier weather than usual and less solar radiation.

The energy bills 

Across twelve months the total electricity bill for the house came to €332 — an average of €28 a month. That is the whole bill: heating, cooling, hot water, ventilation, lighting, appliances and PHEV car charging, for a household of three adults and two young children.

The shape of it matters as much as the total. June, July and August cost nothing at all, because generation and export credits covered everything the house drew. April and May came in at €2 and €1. The bills only become visible in the depths of winter, peaking at €95 in January and €94 in December, when generation falls to roughly a third of its summer level and the house draws more from the grid. Even then, a €95 winter electricity bill for an all-electric four-bedroom house is not a number most people are used to seeing.

Bar chart of monthly electricity bills at Can Naiades, showing three months at zero euros
Monthly electricity bill across the year. Three summer months came in at zero.
Vista aérea de Can Naiades con la instalación fotovoltaica en cubierta y el Montseny al fondo
The 8.5 kWp rooftop array, 21 panels, paired with a 13.8 kWh battery. 
Cuarto técnico de Can Naiades con el equipo de ventilación con recuperación de calor y la bomba de calor
The plant room: balanced ventilation with heat and moisture recovery, and a high-efficiency heat pump. No boiler, no combustion.

What a year of living here has taught us 

Three things stand out.

The first is that a well-calibrated model is worth the effort. Landing within 2% on consumption over a full year is not luck; it is what happens when the climate data and the occupancy reflect reality. It also means we can now trust the model when it tells us something about a future year, or about a design change we are considering.

The second is that the building fabric does the heavy lifting, and the systems stay small. There is no boiler and no combustion anywhere in the house. There is one split unit, a couple of towel rails, and a ventilation unit that runs quietly in the background — and how the ventilation unit has actually performed is a story in its own right. The comfort does not come from the kit; it comes from insulation, airtightness, glazing and shading getting the conditions close to right before any system is asked to do anything.

The third is that the numbers only tell part of it. Stable temperatures, no draughts, no radiators taking up wall space, quiet rooms and air that stays fresh are things you notice daily and stop being able to measure. We wrote about that in more detail after our first winter.

The short version 

  • 11,929 kWh generated over the year, against 7,835 kWh consumed including PHEV charging — 52% more produced than used
  • 85% of all consumption covered on site by solar PV and battery storage, with just 1,149 kWh drawn from the grid
  • 3,815 kWh net exported to the grid
  • €332 of electricity for the whole year, averaging €28 a month, with three months at zero
  • Measured consumption within 1.6% of the calibrated PHPP prediction, and generation 7% ahead of it

A Passivhaus Plus home is not a theoretical proposition. This one has now run for a year, and the meters agree with the design.

Can Naiades is certified Passivhaus Plus and Near Zero CO₂. Praxis Resilient Buildings delivered the Passivhaus design, site supervision, preliminary Blower Door testing, thermal bridge calculations, dynamic hygrothermal modelling with WUFI and the HVAC system design.

Vista exterior de Can Naiades al atardecer con los interiores iluminados, un año después de su finalización
Can Naiades, one year on. 

Butech Modfacades – Passivhaus Component

Passivhaus Component certification of Butech–Porcelanosa Modfacades, with 3D/2D thermal simulations and optimisation of 15 construction details by Praxis.

Butech – Porcelanosa Modfacades – Passivhaus Component Certification

Passivhaus Certification

Praxis cabecera proyectos

Description

The Butech–Porcelanosa Modfacades modular steel-frame system has achieved Certified Passive House Component status for the warm-temperate climate zone.

The industrialised system combines a ventilated façade, several layers of mineral wool insulation, an airtight board and an insulated internal service void. The external wall achieves a certified U-value of 0.19 W/m²K, and all assessed junctions meet the hygiene criterion for minimum internal surface temperature.

Praxis Resilient Buildings carried out 3D and 2D finite-element thermal simulations using Dartwin Mold Pro 3D and Flixo Pro. These quantified the impact of the steel frame, anchor plates and structural connections that penetrate the insulation.

Praxis calculated and optimised 15 standardised construction details. These cover wall, roof and floor junctions, plus window installations with insulated preframes and shutter boxes. Praxis also managed the full certification process with the Passive House Institute. The certification confirms Modfacades as a high-performance industrialised envelope solution for energy-efficient buildings in warm-temperate climates.

  • Year: 2026
  • Location: Vila-real
  • Services: Passivhaus component certification; 3D thermal bridge calculations; 2D thermal bridge calculations

EnerPHit Unit Retrofit, Donostia

First EnerPHit Unit apartment retrofit in Donostia-San Sebastián: an 88 m² flat upgraded from inside with wood-fibre insulation, MVHR and triple glazing.

Etxea Laura eta Martin: EnerPHit Unit Apartment Retrofit in Donostia-San Sebastián

Passivhaus certification

Praxis cabecera proyectos

Description

Etxea Laura eta Martin is an EnerPHit Unit certified apartment retrofit in Donostia-San Sebastián, Spain. The 88 m² home is in a 1965 building with a concrete frame and masonry infill. All the work was done from inside the flat, with no changes to the façade.

The deep energy retrofit relied on a few simple measures that can be repeated in other flats. The external walls combine 40 mm of internal wood-fibre insulation with insulation to the existing cavity, reaching U = 0.20 W/(m²K). The floor build-up includes 80 mm of wood fibre. Certified Smartwin triple-glazed windows achieve an installed Uw of 0.90 W/(m²K). The airtight layer is continuous repaired plaster, carefully detailed around the existing shafts and pipes. It reached n50 = 0.9 h⁻¹ at the first blower-door test.

An MVHR unit provides 77% effective heat recovery. Space heating comes from a 1 kW electric post-heater in the supply air. Domestic hot water is produced by a ducted air-to-water heat pump, so the gas connection could be removed.

PHPP gives a heating demand of 23 kWh/(m²a) and a renewable primary energy (PER) demand of 63 kWh/(m²a). After 18 months in the home, the owners report steady 21 °C winter temperatures, excellent air quality and electricity costs of around €600–700 a year.Architecture and PH Design: Martin Johnson – Oreka Arkitektura
Building Services: Iturri Iturgintza
PH Certification: Oliver Style – Praxis Resilient Buildings

Web iPHa: https://passivehouse-database.org/details/8056

Photos & renders: Martin Johnson – Oreka Arkitektura

  • Year: 2025
  • Location: Donostia-San Sebastián, Spain
  • Architecture: Martin Johnson – Oreka Arkitektura
  • Services provided by Praxis: Passivhaus certification EnerPHit Unit
  • Passivhaus Certification Class: EnerPHit Unit
  • Climate zone: Warm-temperate
  • Floor area: 88 m2
  • Thermal envelope area: 236 m2
  • Blower Door result: 0.85 h⁻¹
  • Heating Demand: 23 kWh/m2·a
  • Cooling Demand: (no active cooling)
  • Primary Energy Renewable consumption: 63 kWh/m2·a
  • Final Energy consumption: 50 kWh/m2·a
  • Renewable energy generation: 0 kWh/m2·a
  • CO2eq emissions: 18 kg/m2·a

Blower Door Test, Cold Storage Facility

Blower Door airtightness testing and air leakage detection for a −20°C cold storage facility at an industrial plant near Barcelona.

Cold Storage Facility Blower Door Test, Barcelona

Blower Door

Praxis cabecera proyectos

Description

Praxis Resilient Buildings carried out a Blower Door airtightness test on a cold storage facility at an industrial plant in Lliçà d’Amunt, Barcelona. The tested area was a freezer room designed to operate at −20°C, with an internal volume of 119.79 m³ and an envelope area of 148.28 m².

Significant ice build-up had been occurring on the internal walls and ceiling due to the infiltration of warm, moisture-laden air from adjacent areas. The objective of the test was to measure the freezer room’s overall air permeability, locate the principal air leakage paths and recommend targeted remedial measures.

The test was performed under depressurisation in accordance with ISO 9972, using calibrated fan pressurisation equipment. At a reference pressure of 50 Pa, the measured air leakage rate was 163 m³/h, equivalent to an air permeability of qE50 = 1.10 m³/(h·m²) and an air change rate of n50 = 1.36 h⁻¹. The test data met all ISO 9972 validity requirements, including those relating to the pressure range, number of measurement points, airflow exponent and coefficient of determination.

The measured air permeability was slightly above the project target of qE50 ≤ 1.00 m³/(h·m²), established with reference to BSRIA Specification 10/98. A detailed air leakage investigation was therefore undertaken using a hot-wire anemometer and thermal imaging camera. Air leakage was identified around the pressure-relief fan, sliding entrance door, corner finishing profiles and shelving brackets. Targeted sealing recommendations established clear priorities for remedial airtightness work, with the aim of reducing moisture ingress and ice formation while improving temperature control, thermal performance and operational efficiency.

  • Year: 2025
  • Location: Lliça d’Amunt, Barcelona
  • Services: Blower Door

Barcelona office Blower Door tests

Blower Door tests in a Barcelona office building, identifying air leakage in staircase and lobby pressurisation systems to support fire safety.

Barcelona office Blower Door tests

Blower Door

Praxis cabecera proyectos

Description

Blower Door testing of staircase and lobby pressurisation systems in a Barcelona office building

Praxis carried out six Blower Door airtightness tests in an office building located on Passeig de Gràcia in central Barcelona. The tests assessed the main staircase and five basement lobbies connected to two mechanical pressurisation systems.

Staircase pressurisation systems are an important part of a building’s fire-safety strategy. By maintaining positive pressure within protected escape routes, they help prevent smoke from entering during a fire. However, excessive air leakage through doors, construction joints or ventilation ducts can prevent the system from achieving the required pressure difference.

The tests were conducted in pressurisation mode in accordance with ISO 9972. Smoke testing and an anemometer were used at approximately 50 Pa to locate leakage paths, followed by multi-point measurements to quantify airflow.

In the staircase, the main air leakage occurred through the rooftop smoke vents and their perimeter frames, accounting for approximately 38% of the measured airflow at 50 Pa. In the basement lobbies, leakage was identified around timber panelling, construction junctions, ventilation grilles, drop seals and sliding fire-resistant doors. The investigation identified priority airtightness improvements to enhance the reliability of the pressurisation systems and support fire safety.

  • Year: 2022
  • Location: Passeig de Gracia, Barcelona
  • Services Blower Door

Cooling the World Cup: USA vs Qatar

Only three U.S. World Cup venues can genuinely be described as actively cooled match stadiums: Atlanta, Dallas and Houston.

Cooling the World Cup: USA vs Qatar

Two approaches to conditioning large football stadiums in warm climates.

Only three U.S. World Cup venues can genuinely be described as actively cooled match stadiums: Atlanta, Dallas and Houston. The key point is not concourse air-conditioning, but the ability—when the retractable roof is closed—to condition the spectator bowl and pitch as one large indoor volume. 

Cooling the World Cup: USA vs Qatar

This is effective, but not subtle. The U.S. strategy is to enclose first and cool second. Qatar 2022 used a different logic: architectural form, air movement and local supply to create cooled microclimates around spectators and the pitch. The real comparison is therefore not whether cooling works, but how efficiently, evenly and robustly it delivers comfort, using the least possible energy. 

Is active cooling necessary in football stadiums? 

In June and July, outdoor temperatures in Atlanta, north Texas and Houston can exceed 35°C / 95°F. Atlanta and Dallas have similar absolute humidity, around 17 g/m³, while Houston is closer to 20 g/m³, meaning roughly 20% more moisture in the air. Houston is therefore the most latent-load driven case: the plant must remove water vapour as well as heat. 

For players, high wet-bulb conditions reduce evaporative heat loss, increase cardiovascular strain and can reduce high-intensity running. For spectators, long dwell times, queuing, alcohol consumption and limited personal control turn heat into a crowd-safety issue. Cooling is therefore part of the event strategy, not a luxury. The weakness is that it depends on treating each stadium as a sealed building: roof open, doors open, uncontrolled solar gains or leakage at the retractable roof perimeter all make the cooling task less elegant and more energy intensive. 

Estadio de Atlanta

Atlanta Stadium: integrated, but still a huge, conditioned volume 

Atlanta is the most integrated of the three. Its retractable roof closes the bowl, and the stadium combines daylighting, automated controls, LED lighting and a wider sustainability narrative. It is closest to a whole-building proposition rather than simply a stadium with a very large chiller plant. 

The cooling principle is still conventional: reduce air exchange, enclose the volume, and condition it with high-capacity HVAC. This should give stable operative temperatures once the roof is closed. The limitation is the envelope: a large roof aperture, translucent roof elements and a very high internal volume all carry thermal penalties. It may be efficient by U.S. mega-venue standards, but that is a low bar compared with reducing the conditioned volume or supplying comfort locally. 

Dallas Stadium: effective comfort, blunt energy logic 

Dallas is the clearest expression of the U.S. model: close the roof and operate the stadium as a giant air-conditioned arena. Reported closed-roof conditions are around 22–24°C / 72–75°F even when outdoor temperatures are close to 35°C / 95°F and perceived outdoor conditions approach 41°C / 106°F. Technically, that is a successful comfort outcome.  The cost is energy intensity. Published estimates put Dallas close to 100,000 kWh per match for air-conditioning. In U.S. energy terms, that is about 341 million BTU of electrical input per match before considering plant efficiency and distribution losses. Even allowing for uncertainty, the order of magnitude is telling: comfort is delivered primarily by plant capacity, not by climatic intelligence. The system works, but success is bought mechanically. 

Estadio de Dallas
Estadio de Houston: la advertencia más clara sobre la envolvente

Houston Stadium: the clearest envelope warning 

Houston is the hardest case because heat and humidity combine. With the roof closed, the stadium can act as a conditioned bowl and protect spectators from direct sun and rain. But it also shows why ‘retractable roof’ and ‘thermal envelope’ are not the same thing. The stadium performs well only when the roof and major openings are treated as a serious thermal boundary.  When the roof is open, solar exposure is uneven: south and west areas are generally more protected, while north and east areas are more exposed. This matters because mean radiant temperature can rise even if the air temperature is acceptable. In those conditions, internal shading and strict roof/opening control become part of the cooling strategy, not operational footnotes. Air leakage, roof perimeter gaps, large volumes and solar penetration all reduce the effectiveness of mechanical cooling.

Qatar 2022: targeted microclimate rather than cooled void 

Qatar’s strategy was fundamentally different in the 2022 world cup. It did not attempt to cool an entire stadium void. The principle was spot cooling: supply cool air where people and players actually are, through grilles in the stands and larger pitch-side nozzles. Stadium form, insulation, air recirculation, filtration, wind-tunnel testing and CFD were used to contain a cooled microclimate within a semi-open condition. 

This is a more interesting comfort strategy because it starts from the occupied zone: the spectator’s ankles, the occupied tier, the player and the pitch boundary layer. It also recognises that comfort depends on radiant temperature and air movement, not only dry-bulb temperature. The U.S. approach is simpler and probably more robust operationally: close the roof, set a temperature, run the plant. But it cools a very large volume whether or not each cubic metre contributes to comfort. Qatar’s approach was not free of energy or carbon questions, but conceptually its efficiency argument is stronger because comfort was targeted rather than volume-wide. 

Qatar 2022: microclima dirigido en lugar de enfriar el vacío
Qatar 2022: microclima dirigido en lugar de enfriar el vacío

What monitored data is available? 

The evidence base is thinner than it should be. For the U.S. venues, the best public energy figures are estimates rather than confirmed BMS or utility-meter data: approximately 99,925 kWh per match for Dallas, 97,344 kWh for Houston and 96,020 kWh for Atlanta. Dallas also has a reported internal range of 22–24°C / 72–75°F, but without relative humidity, air speed, radiant temperature or sensor locations, this is not a full comfort dataset. 

For Qatar, the public evidence is technically richer—CFD, wind-tunnel work, targeted supply, air recirculation and reported target conditions around 18–24°C / 64–75°F—but still not equivalent to transparent post-occupancy monitoring. One CFD-based study reported acceptable comfort under external conditions up to 48°C / 118°F and 70% relative humidity, with many zones maintaining thermal neutrality even when cooling load was reduced by about 50%. That supports the design logic, but it remains modelled evidence, not match monitoring. 

A rigorous comparison—kWh per spectator-hour, kWh per comfort-hour, or WBGT reduction per kWh—is therefore not possible from public sources. The available evidence suggests that U.S. closed-roof cooling works, while Qatar’s strategy is conceptually more energy efficient. But neither case has yet published enough monitored data to prove performance transparently. 

Lessons learned 

First, enclosure works only if it is treated seriously. A retractable roof becomes a thermal envelope only when airtightness, solar control, perimeter detailing and operational discipline are adequate. 

Second, comfort must be measured at the occupant, not the thermostat. Air temperature alone is insufficient; radiant temperature, humidity, air speed, stratification and crowd density all matter. 

Third, energy efficiency depends on reducing load before increasing plant size. Qatar’s hierarchy—shade, shape, contain, supply locally, recirculate, then cool—is better environmental design. The U.S. model starts further downstream: close the lid and cool the room. 

The conclusion is simple: Atlanta, Dallas and Houston can host safe, comfortable matches, but they should not be mistaken for low-energy precedents. The best cooling strategy is not a bigger chiller. It is a better solar control, better scheduling (i.e. hosting games at cooler hours of the day) and a better envelope.

Classroom overheating in Barcelona: HVAC simulation study

EnergyPlus simulation study on classroom overheating in Barcelona, thermal comfort, solar orientation and HVAC strategies for schools.

Classroom overheating in Barcelona: HVAC simulation study

Prevención del sobrecalentamiento en aulas: un estudio de simulación termodinámica en Barcelona
Plano aula

Introduction: why classroom overheating matters

As climate change intensifies summer heatwaves, preventing classroom overheating has become a critical design challenge for educational buildings in Mediterranean cities such as Barcelona. Schools must provide healthy, comfortable indoor conditions while also reducing energy consumption and operational complexity.

This article presents a thermodynamic building simulation study assessing overheating risk in two primary-school classrooms in Barcelona. The analysis uses DesignBuilder with the EnergyPlus calculation engine to evaluate whether a centralised 100% outdoor air HVAC system can maintain thermal comfort during school hours from May to September.

The study is relevant for architects, engineers, school operators and public authorities seeking evidence-based strategies for thermal comfort in schools, especially where cooling is delivered through a central air-handling unit rather than room-by-room terminal units.

* Schools shut in Spain from the end of June until September. However, for the simulations, July and August were included in the simulations, to have results under more challenging climate conditions. This was also done as the climate file is based on historical data. Currently, weather conditions that typically occurred in July now often occur in May.

Study objectives

The simulation was designed to answer three practical questions about classroom overheating, supply-air temperature and the impact of solar orientation.

  • How do east- and west-facing classrooms behave differently due to solar exposure, and what does this mean for HVAC control?
  • How many teaching hours exceed an operative temperature of 27°C despite cooled air being supplied at 14°C?
  • What relationship between outdoor temperature and supply-air temperature helps avoid both overheating and overcooling?

Simulation tools and building model

The dynamic simulation was carried out in DesignBuilder using the EnergyPlus engine. The model represents two identical classrooms located on the third floor of a primary school in Barcelona: one facing east and one facing west, with a north–south corridor between them.

The Barcelona–Airport IWEC II weather file developed by ASHRAE was used for the climate assumptions. July and August were included in the simulation period even though schools in Spain typically close during summer holidays, because these months provide a more demanding stress test for the system and help evaluate future climate resilience.

Internal floors and partitions were modelled as adiabatic. The envelope parameters comply with the minimum requirements of Spain’s CTE HE1 code for Climate Zone C. Windows are double glazed with Ug = 1.80 W/m²K, 79% visible transmittance and a solar factor of 59%. The external wall has U = 0.49 W/m²K, the roof has U = 0.40 W/m²K and air permeability is n50 = 3 ach.

Each classroom includes fixed external shading devices with a 50% reduction factor, representing expanded metal mesh shading. This shading reduces solar gains but does not eliminate the impact of orientation.

Internal loads and HVAC configuration

Each classroom has a floor area of 60 m² and is occupied by 31 pupils and one adult teacher during school hours. Lighting and equipment loads operate during teaching hours, Monday to Friday from 08:00 to 18:00, although lighting is assumed to be off during summer.

Ventilation is provided by a central air-handling unit supplying 100% outdoor air at 45 m³/h per person, equivalent to 1,395 m³/h per classroom. The system includes heat recovery with 79% sensible efficiency and 62% latent efficiency.

Cooling is provided by an air-to-water heat pump producing chilled water at 7°C for the AHU cooling coil. During summer school hours, the supply air temperature is assumed to be a constant 14°C at classroom supply level. In practice, duct heat gains and pressure losses may mean that the delivered supply air temperature and airflow differ from the simulation assumption. For May and September, a dual-setpoint control strategy is used to reduce overcooling: when outdoor temperature is below 16°C, supply air is delivered at 20°C; when outdoor temperature rises above 17°C, supply air is delivered at 14°C.

Internatl confort range

Thermal comfort criteria

Thermal comfort was assessed using operative temperature thresholds during school hours only. The comfort band was defined as 22°C to 27°C, with indoor relative humidity targets between 30% and 60% at 26°C. Conditions below 22°C were classified as too cold, while conditions above 27°C were classified as too hot.

Using operative temperature rather than air temperature alone provides a more representative assessment of how occupants experience the room, because it accounts for both air temperature and radiant temperature from surrounding surfaces.

Key results: overheating and overcooling risk

External Climate Overview (08:00–18:00, Mon–Fri)

The analysis shows that the central HVAC system generally maintains classroom comfort for most teaching hours. However, the results also demonstrate that orientation, solar gains and supply-air control are decisive factors in determining real comfort performance.

Key Results
Overheating Risk – Summary (% of teaching hours > 27 °C)

The east-facing classroom experiences the highest overheating risk, particularly in July and September, because morning solar gains coincide with early occupancy and rising outdoor temperatures. In July, the east classroom exceeds 27°C during approximately 7% of teaching hours despite the supply air being delivered at 14°C.

Overcooling Risk – Summary (% of teaching hours < 22 °C)

The west-facing classroom performs slightly better in terms of overheating, with only a small proportion of hours above 27°C in September. However, it is more exposed to overcooling in the morning during shoulder months, because delayed afternoon solar exposure does not compensate for early cool supply air.

This finding illustrates a common HVAC design challenge in schools: a single central control strategy can perform adequately on average while still creating different comfort outcomes across zones with different orientations.

Classroom overheating in Barcelona: HVAC study – Figure 9
Classroom overheating in Barcelona: HVAC study – Figure 10
Classroom overheating in Barcelona: HVAC study – Figure 11
Classroom overheating in Barcelona: HVAC study – Figure 12
Classroom overheating in Barcelona: HVAC study – Figure 13
Classroom overheating in Barcelona: HVAC study – Figure 14
Classroom overheating in Barcelona: HVAC study – Figure 15
Classroom overheating in Barcelona: HVAC study – Figure 16
Classroom overheating in Barcelona: HVAC study – Figure 17

Why orientation matters in classroom comfort

Solar orientation plays a significant role in overheating risk. East-facing classrooms receive direct solar radiation in the morning, when pupils arrive and classrooms are already occupied. This can quickly raise operative temperatures before the cooling system has fully compensated for the solar load.

West-facing classrooms receive more delayed solar radiation in the afternoon. This can reduce early-morning overheating risk but may create a different comfort profile later in the day. In the simulation, the west classroom was also more prone to mild overcooling during May and September.

For school buildings in Barcelona and other Mediterranean climates, façade orientation should therefore be considered alongside HVAC design. Identical classrooms can require different control strategies even when they have the same area, occupancy and envelope specification.

Recommended strategies to prevent classroom overheating

The simulation confirms that HVAC control is important, but it should be combined with passive design measures to create resilient school buildings. The most effective design approach is to reduce heat gains first, then use efficient mechanical systems to manage the remaining cooling load.

  • Improve external shading, especially on east and west façades where low-angle solar radiation is difficult to control.
  • Optimise glazing specifications, particularly solar factor, visible transmittance and frame performance.
  • Improve airtightness and insulation to reduce unwanted heat transfer and improve system predictability.
  • Reduce internal heat gains from lighting, equipment and operational schedules.
  • Consider night ventilation or free-cooling strategies where climate, acoustics and security conditions allow.
  • Commission airflow rates and supply-air temperatures carefully at classroom level rather than only at the AHU.

HVAC design lessons for schools

For 100% outdoor air systems serving multiple classrooms, ductwork design and commissioning are critical. Long duct runs can introduce pressure losses and heat gains, reducing airflow and increasing supply-air temperature at the classroom grilles. These effects can be especially important when the design relies on cool supply air to manage sensible loads.

The study also highlights the value of simple but intelligent control logic. A dual-setpoint strategy based on outdoor temperature can reduce overcooling in shoulder months without adding excessive complexity. However, zone-level monitoring or balancing may still be needed when classrooms have very different orientation or solar exposure.

Energy simulation with tools such as EnergyPlus and DesignBuilder allows design teams to test these strategies before construction or refurbishment. This supports better decisions, reduces performance gaps and helps align thermal comfort with energy-efficiency objectives.

Conclusions

The results show that a centralised 100% outdoor air HVAC system can generally maintain acceptable comfort in classrooms in Barcelona, but overheating risk is not eliminated. The east-facing classroom remains more vulnerable to overheating, especially in July, while the west-facing classroom shows a greater tendency toward mild overcooling during shoulder-season mornings.

Preventing classroom overheating requires a combined strategy: accurate energy simulation, façade-specific passive design, robust HVAC controls and careful commissioning. For Mediterranean school buildings facing warmer and more variable climate conditions, this integrated approach is essential for health, comfort, educational performance and energy efficiency.

FAQ: classroom overheating and thermal comfort

What causes classroom overheating?
Classroom overheating is caused by a combination of high outdoor temperatures, solar gains through windows, internal heat gains from pupils and equipment, insufficient shading and poorly matched HVAC control.

How can overheating in schools be prevented?
The most effective approach combines passive measures such as external shading, better glazing and reduced internal gains with HVAC strategies such as adaptive supply-air temperature control and careful commissioning.

What is a comfortable classroom temperature?
In this study, the comfort range was defined as an operative temperature between 22°C and 27°C during occupied school hours.

Why use EnergyPlus for school overheating studies?
EnergyPlus enables hourly dynamic simulation of weather, occupancy, solar gains, envelope performance and HVAC operation, making it suitable for evaluating overheating risk before decisions are implemented on site.

Terrassa Hospital Blower Door tests

Blower Door airtightness testing in 17 isolation ward rooms at Hospital de Terrassa, Barcelona, to EN 13829 / ISO 9972 for infection-control risk assessment.

Terrassa Hospital Blower Door tests

Blower Door

Praxis cabecera proyectos

Description

Blower Door Airtightness Testing in Hospital Isolation Rooms — Hospital de Terrassa, Barcelona

Praxis carried out Blower Door airtightness tests in 17 hospital bedrooms in the isolation ward of the Hospital de Terrassa, Barcelona, as part of the verification of spaces designed to accommodate patients with infectious diseases.

The objective of the testing was to measure the air permeability of individual isolation rooms and support an assessment of the potential risk of aerosol contamination between rooms and adjacent hospital areas. The test strategy was informed by BSRIA BTS 3/2018 — Air Permeability Testing of Isolation Facilities, which provides guidance for assessing air leakage in isolation facilities.

Testing methodology

The airtightness tests were carried out using fan pressurisation equipment in accordance with EN 13829 (now superseded by ISO 9972). Each room was tested in both depressurisation and pressurisation, with measurements taken between approximately 20 Pa and 70 Pa.

Results

The results were considered satisfactory, with no room showing excessive air permeability according to the project assessment. The testing provided useful evidence for the commissioning and risk assessment of the isolation ward, supporting the control of unintended air leakage paths between patient rooms and surrounding hospital spaces.

This type of airtightness testing helps support infection-control strategies, ventilation commissioning, and risk assessment for airborne contamination in healthcare environments.

  • Year: 2021
  • Location: Terrassa, Barcelona
  • Services: Blower Door