Barcelona office Blower Door tests
Blower Door tests in a Barcelona office building, identifying air leakage in staircase and lobby pressurisation systems to support fire safety.
Barcelona office Blower Door tests
Blower Door

Description
Blower Door testing of staircase and lobby pressurisation systems in a Barcelona office building
Praxis carried out six Blower Door airtightness tests in an office building located on Passeig de Gràcia in central Barcelona. The tests assessed the main staircase and five basement lobbies connected to two mechanical pressurisation systems.
Staircase pressurisation systems are an important part of a building’s fire-safety strategy. By maintaining positive pressure within protected escape routes, they help prevent smoke from entering during a fire. However, excessive air leakage through doors, construction joints or ventilation ducts can prevent the system from achieving the required pressure difference.
The tests were conducted in pressurisation mode in accordance with ISO 9972. Smoke testing and an anemometer were used at approximately 50 Pa to locate leakage paths, followed by multi-point measurements to quantify airflow.
In the staircase, the main air leakage occurred through the rooftop smoke vents and their perimeter frames, accounting for approximately 38% of the measured airflow at 50 Pa. In the basement lobbies, leakage was identified around timber panelling, construction junctions, ventilation grilles, drop seals and sliding fire-resistant doors. The investigation identified priority airtightness improvements to enhance the reliability of the pressurisation systems and support fire safety.