Is your wall as good as the calculation says? Measuring U-values in situ, and why it matters in retrofit

How to measure a wall’s U-value in situ to ISO 9869: the kit, the set-up, the maths, and what UK test walls revealed about retrofit.

Is your wall as good as the calculation says? Measuring U-values in situ, and why it matters in retrofit

A calculated U-value is a promise. An in-situ measurement to ISO 9869 tells you whether the wall keeps it, provided the test is set up properly.

Navy graphic with a white line settling at a measured U-value of 0.49, well above a gold dashed line marking the calculated 0.26.
Measured against calculated: the reference cavity wall at the HIVE lost almost twice the heat its calculation predicted.

Every energy calculation starts with assumptions about the walls: what they are made of, how well each layer conducts heat, and how carefully it was all put together. Usually nobody checks. A recent EU-funded market surveillance campaign suggests someone should. Insulation samples were bought in 14 European countries and tested in the laboratory. For thermal resistance, 31 of the 97 samples tested (32%) did not meet the requirements.

A product sample in a laboratory is not a wall, of course. The product is only one link in the chain; workmanship, moisture and the existing fabric you build onto are the others. The only way to see the whole chain at once is to measure the finished wall where it stands. This article explains how to do that to ISO 9869-1: the kit you need, how to set it up so the result means something, and the calculation behind it. It then looks at what a set of test walls in the UK showed about the gap between calculated and measured U-values, especially in retrofit.

The message is simple: you can’t improve what you don’t measure. So if you measure, get it right.

32%

of insulation samples failed on thermal resistance

+88%

reference wall against its calculation

14–28%

ISO 9869 uncertainty, even done well

1–3 weeks

typical test duration

Calculated and measured U-values

A U-value is the rate at which heat passes through one square metre of a building element for each degree of temperature difference across it, in W/m²K. Normally it is calculated to ISO 6946 from the thickness and thermal conductivity of each layer. This is the method behind PHPP and most national energy calculation tools.

An in-situ measurement to ISO 9869-1 takes the opposite route. It records the heat flowing through the real wall, and the temperatures on either side, over several days, and divides one by the other.

Both have their place. A calculation is quick and works at design stage, but it is only as good as its inputs. A measurement is slow and needs the right conditions, but it tells you what the wall actually does, including everything nobody wrote down.

The kit

The equipment is modest:

  • a datalogger recording every 5, 10 or 30 minutes;
  • air temperature probes inside and outside (Ti and Te);
  • at least two heat flux plates on the inside surface, measuring W/m²;
  • two thermocouples on the inner and outer surfaces (Tsi and Tse);
  • a heater to keep the indoor temperature high and steady.

Two heat flux plates rather than one matters. Each plate measures a single spot, and ISO 9869 attributes around 5% of the uncertainty to small differences in how well each plate contacts the wall. Averaging two or more plates reduces that.

Diagram of a wall section showing heat flux plates and temperature sensors on the inside face, an outdoor temperature sensor, a heater and a datalogger.
The kit for an in-situ U-value measurement to ISO 9869: datalogger, indoor and outdoor air temperature probes, heat flux plates and surface thermocouples, plus a heater to hold the indoor temperature. Click to enlarge.

Some handheld instruments skip the heat flux plate altogether. The temperature-based method measures the air and inner surface temperatures and assumes a standard surface resistance to estimate the heat flow. It is quicker and cheaper, but it is not an ISO 9869 method, and it is fragile: in a well-insulated wall the inner surface is barely a degree cooler than the room, so small errors swing the result. At the HIVE, run alongside the heat flux plates, it gave 0.33 W/m²K for the ISOBIO panel where the plates gave 0.17, and 0.97 for the solid brick wall where the plates gave 2.46, yet matched them almost exactly on the external retrofit. A 2018 university comparison on a refrigerator wall found the same kind of gap: 0.26 against 0.39.

Setting it up so the result means something

Most bad measurements are decided before the logger is switched on.

The plates go on the inside face, away from radiators, draughts, furniture and direct sun. Look at the wall with a thermal camera first, to find an area that represents what you want to measure. In a timber-frame wall, decide whether that is the insulation between the studs or the wall including its studs, and compare the result with the matching calculation.

The temperature difference across the wall should be as large and as steady as possible. That means testing in the heating season, with a heater holding the room temperature constant. In the test described below, the room averaged 25.6 °C while outdoors averaged 2.4 °C, a difference of more than 23 K. A summer test at the project’s sister demonstrator in Seville shows the opposite case. The temperature difference was small and the data never settled into a result anyone could stand behind. North-facing or shaded walls are best, because sun on the outer surface distorts the readings.

Then let the data decide when to stop. ISO 9869 sets the rules:

  • Light elements (below 20 kJ/m²K): analyse night-time data only, and stop when three consecutive nights agree within ±5%.
  • Heavier elements: run the test for at least 72 hours, in whole 24-hour cycles. The final thermal resistance must be within ±5% of the value 24 hours earlier. The result from the first two-thirds of the test must agree within ±5% with the last two-thirds.

In practice, plan on one to three weeks.

A red circular heat flux sensor fixed to a clay-plastered wall panel inside a test cell, with a laptop and datalogger in the foreground.
Heat flux plate and surface sensors on the inside face of the ISOBIO test panel at the HIVE, Wroughton.

The calculation

ISO 9869’s average method is just what it sounds like. The measured U-value is the sum of all heat flux readings divided by the sum of all indoor-to-outdoor temperature differences: U = Σq / Σ(Ti − Te). Plotted as a running value, it wanders at first and then converges. The heat flux plate’s own small thermal resistance slightly disturbs the heat flow it measures, and a correction is applied for it.

Then comes the part most reports leave out: uncertainty. Even with everything done properly, ISO 9869 estimates the total uncertainty at between 14% and 28%. It is built up from:

  • calibration;
  • sensor contact;
  • the plate’s disturbance of the heat flow;
  • variations over time;
  • the difference between air and radiant temperatures.

So a few per cent between measured and calculated values counts as agreement. Forty per cent does not.

The case study: the ISOBIO test walls at the HIVE

ISOBIO was a Horizon 2020 project that ran from 2015 to 2019. It developed insulation and renders made from plant fibres, agricultural by-products and bio-based binders, aiming for 50% less embodied energy than petroleum-based insulation. The ISOBIO consortium built the materials into a prefabricated wall panel and installed it at the HIVE, the University of Bath’s test facility in Wroughton, alongside conventional reference walls. Each cell was instrumented and logged at five-minute intervals.

The panel is 332 mm thick, in eight layers:

  1. 25 mm lime-hemp render;
  2. 50 mm rigid hemp insulation board;
  3. 145 mm timber studs filled with hemp, cotton and flax insulation;
  4. 12 mm OSB board;
  5. an airtight membrane with variable vapour resistance;
  6. a 45 mm insulated service void, with its battens turned 90° to the studs;
  7. 40 mm compressed straw board;
  8. 15 mm clay-hemp plaster.

In the calculation, each material’s thermal conductivity was adjusted to its moisture content at 50% relative humidity, rather than taken dry.

To-scale horizontal section of a prefabricated timber panel with eight numbered layers, from external render to internal plaster.
The layers of the ISOBIO new-build panel, 332 mm in total. Click to enlarge.

Good agreement: the new-build panel

The panel was measured from 24 February to 14 March 2018: 432 hours and 18 days of five-minute readings. The measured U-value was 0.169 W/m²K. The calculated value for the insulated section between the studs, which is where the sensors sat, was 0.159 W/m²K. The difference is 6.6%, well within the measurement uncertainty, and all three ISO conditions were met.

Taken alone, a 12-hour window of night-time data would have given 0.19 W/m²K. That shows why a short test misleads and a full one settles.

Line graph of two running measured U-values over 18 days, each beside a dashed line for its calculated value; the lower pair agrees closely, the upper pair is far apart.
Same weather, same 18 days: the ISOBIO panel settles on its calculated U-value, while the reference cavity wall settles almost twice as high. Measured data, 24/02–14/03/2018. Click to enlarge.

Poor agreement: the walls nobody thought to question

The reference new-build cavity wall was measured over the same period and under the same conditions. It is conventional UK construction: brick, a low-emissivity cavity, rigid PIR insulation board and lightweight concrete block. It measured 0.49 W/m²K against a calculated 0.26, a deviation of 88%, in a test that met every ISO condition. A wall of standard construction was losing almost twice the heat its calculation predicted. The measurement cannot say why; it only shows that the figure on paper was wrong.

The existing solid brick wall was measured in December 2017 and fared little better: 2.46 W/m²K measured against 1.74 calculated, a deviation of 41%.

Bar graph of the deviation between measured and calculated U-values for five walls; only the ISOBIO new-build panel falls within the ±14% band.
Measured against calculated U-values for the five UK test walls, with the ISO 9869 uncertainty band. Click to enlarge.
Inside face of a lightweight concrete block wall in a test cell, with sensor cables at the edge.
The reference new-build cavity wall at the HIVE, seen from inside.

The retrofits: misses in both directions

Both ISOBIO retrofit systems were then fitted to the reference walls. This time the calculations started from the measured existing walls: the conductivity of the old brick was worked back from the 2.46 W/m²K result.

The internal retrofit added about 108 mm to the solid wall: rigid hemp board, compressed straw board and clay plaster. Measured from 9 to 23 November 2018, it achieved 0.554 W/m²K against a calculated 0.704, 21% better than predicted. The wall’s heat loss fell by 77% against a predicted 71%.

Paired bar graph of the solid wall’s U-value before and after retrofit, showing measured and calculated values.
Solid brick wall before and after the ISOBIO internal retrofit, measured against calculated. Measured data, December 2017 and November 2018. Click to enlarge.

The external retrofit added 220 mm to the cavity wall: insulated timber studs, rigid hemp board and lime-hemp render. It was measured from 6 October to 7 November 2018, 768 hours in all. It met the duration and end-stability conditions but only just missed the third, where the first and last parts of the test must agree within 5%, so its uncertainty is wider. It measured 0.222 W/m²K against a calculated 0.152, 46% worse than predicted. Heat loss fell by 55% against a predicted 69%, so only about four-fifths of the expected saving was delivered.

Line graph of the running measured U-value staying well above a dashed line marking the calculated value.
ISOBIO external retrofit: the running measured U-value sits well above the calculated value and is still drifting at the end of the test. Measured data, 06/10–07/11/2018. Click to enlarge.

The five test walls at a glance (U-value in W/m²K)

WallMeasured / calculatedDeviation
ISOBIO new-build panel0.17 / 0.16+7%
Reference new-build cavity wall0.49 / 0.26+88%
Existing solid brick wall2.46 / 1.74+41%
ISOBIO internal retrofit0.55 / 0.70−21%
ISOBIO external retrofit0.22 / 0.15+46%

What this means for retrofit

Put the walls together and a pattern appears. Calculations for existing buildings miss in both directions, by anything from 20% to 90%, and only a measurement tells you which way.

The same thing appears at scale. BRE measured around 300 walls in English homes. On average, solid walls performed 17–33% better than calculated, while insulated cavity walls performed 29% worse. BRE concluded that national insulation programmes were likely to be less effective than the usual assumptions suggested.

This matters because a saving is the difference between two numbers. If the “before” wall is better than you assumed, or the “after” wall is worse, the predicted saving is overstated. The client finds out from the energy bills.

Measuring before a retrofit fixes the baseline and helps size the insulation. A published case study on a listed 16th-century manor in Switzerland shows what that can mean. The uninsulated wall measured 0.77 W/m²K. To reach the subsidy threshold of 0.3, it needed 8 cm of sheep’s wool rather than the 16 cm recommended. That saves floor space and money in a building where insulating inside is the only option.

Measuring after checks the workmanship and closes the loop. As at the HIVE, it also turns guessed material properties into measured ones for the next calculation.

New Passivhaus buildings do not need this as standard. Their modelling is generally reliable, as the ISOBIO panel shows. But when energy use does not add up, a measurement is often the quickest way to find out why.

Conclusion

A steady-state calculation can predict a wall’s performance very well, as the ISOBIO panel showed, provided its inputs are realistic. In new construction they often are. In existing buildings they are mostly assumptions, and the HIVE walls show how far those assumptions can stray. Measuring in situ takes weeks, a cold spell and some discipline, but it is the only way to know what a wall really does before and after you invest in it.

Short version

In-situ U-value measurement to ISO 9869-1 uses heat flux plates and temperature sensors for one to three weeks and, even done well, carries 14–28% uncertainty. The set-up decides the result: inside face, a representative spot, a large and steady temperature difference, no sun. At the HIVE, the bio-based ISOBIO panel measured within 7% of its calculation; a conventional cavity wall measured 88% worse, and two retrofits missed by −21% and +46%. In retrofit, measure before to set the baseline and after to verify the saving.

Want to know how your walls really perform? Talk to us.

Sources

  • European Commission, DG GROW: “EU tests put thermal insulating materials under the spotlight”, 19 October 2026.
  • ISO 9869-1:2014, Thermal insulation — Building elements — In-situ measurement of thermal resistance and thermal transmittance.
  • ISO 6946, Building components and building elements — Thermal resistance and thermal transmittance — Calculation methods.
  • Hulme J., Doran S. (2014), In-situ measurements of wall U-values in English housing, BRE report for DECC.
  • Durrer L., Hendrichs H. (2019), “U-value and mold measurement — potential and technical feasibility of renovation of listed heritage buildings”, Denkmal und Energie 2019.
  • Gualdaroni Sacristán E., Lafuente de Aranzadi D. (2018), “Heat transfer coefficient of a building element. Methods comparison”, project report, OTH Amberg-Weiden.
  • ISOBIO monitoring data, HIVE, Wroughton (2017–2018).

The ISOBIO case study was carried out by Oliver Style, then at Progetic, a partner in the ISOBIO consortium, at the University of Bath’s HIVE test facility. The ISOBIO project received funding from the European Union’s Horizon 2020 programme under grant agreement No 636835.

Retrofit without waiting for the neighbours: an EnerPHit Unit in Donostia

An 88 m² flat in a 1965 block, retrofitted from inside to EnerPHit: no gas, 21 °C all winter and about €900 of electricity a year.

Retrofit without waiting for the neighbours: an EnerPHit Unit in Donostia

The first EnerPHit Unit certified apartment retrofit in Donostia / San Sebastián shows that one flat in an ordinary 1960s block can reach Passive House retrofit quality, without touching the façade and without waiting for the neighbours.

Etxea Laura eta Martin is an 88 m² flat in a 1965 apartment block. Architect and developer Martin Johnson set out to retrofit it to the EnerPHit standard, working unit by unit rather than building by building. Praxis Resilient Buildings certified the project as an EnerPHit Unit in June 2025.

23 kWh/(m²a)

heating demand

0.85/h

n50, passed at the first test

88 m²

flat in a 1965 block, no façade work

3 + 3 months

to design and to build

Deep retrofits of apartment blocks usually stall at the same point: the façade belongs to everyone, so nothing happens until everyone agrees. This project takes the opposite route. Every measure, from insulation and airtightness to ventilation and hot water, was carried out within the walls of a single flat.

That is what the EnerPHit Unit route is for: it applies the EnerPHit retrofit standard to one dwelling inside a larger building, so an owner can act now, and the rest of the block can follow flat by flat.

It was also fast. Martin acted as architect, Passivhaus designer, client and partial self-builder, with three months to develop the design and details before construction and three months to build. As a Passivhaus architect who specialises in natural materials, he also saw the project as a chance to show that EnerPHit is achievable in a flat in a multi-residential block using natural materials, in a reasonable time frame and at a reasonable cost.

One flat, no façade work

Four-storey 1960s apartment block with balconies and palm trees, seen from a curving street.
The 1965 apartment block in Donostia / San Sebastián. The retrofit left the shared façade untouched.

The block has a concrete frame with masonry infill walls, typical of its time. A façade retrofit would have needed the agreement of every owner, so the whole upgrade had to happen inside one flat. That meant working around the neighbours’ shunts, drains and water pipes that run through the unit, with limited space inside for new services. Discontinuous masonry, shutter boxes, concrete columns and beams added further risks to airtightness, thermal continuity and the construction sequence.

The technical strategy reduced those risks to a small set of repeatable operations: an airtight layer coordinated around every existing penetration, each junction and structural thermal bridge assessed individually, and an envelope upgraded from inside with predominantly dry, bio-based build-ups.

The contractor had no previous Passive House experience. Daily toolbox talks on site turned each detail into short, trade-specific tasks, so that every trade knew what the insulation and the airtight layer needed from them.

An envelope built from the inside

External walls

The external walls now reach U = 0.20 W/(m²K). The build-up, from inside to outside:

  1. 15 mm plasterboard
  2. 40 mm wood-fibre insulation on steel studs
  3. The existing plaster, as the airtight layer
  4. 70 mm hollow brick
  5. 120 mm blown mineral wool in the existing cavity
  6. 80 mm hollow brick
  7. The original ceramic cladding

Insulating from the inside changes how an existing wall behaves: the masonry runs colder in winter, so moisture has to be considered alongside energy. Here most of the insulation sits in the existing cavity, and the inner layer is a thin, diffusion-open, bio-based wood-fibre board.

Worker in a dust mask injecting insulation through a hose into holes drilled in a masonry wall, next to metal studs.
Blown mineral wool being injected into the existing cavity of the external walls.
Room under construction with light-brown wood-fibre boards fixed between metal studs along the walls.
Wood-fibre insulation boards on steel studs line the external walls before the plasterboard goes on.

Floor and windows

The floor above the unheated commercial unit received 80 mm of wood-fibre board under oak parquet. The solutions throughout are dry and largely bio-based, which kept the programme short and the site clean.

New triple-glazed, Passive House certified windows reach an installed mean Uw of 0.90 W/(m²K). Each frame was taped into the airtight layer before the reveals were finished, so the windows and the plaster work as one continuous seal. External Venetian blinds shade them in summer.

Thermal bridges and moisture risk

Every junction was entered in the PHPP, including those with a negative or zero contribution, among them ten concrete columns in the façade walls and four at floor and ceiling.

3D thermal bridge calculations were made for the column passing through the insulated floor, giving a point thermal bridge of 0.405 W/K. The same assessment checked the inside surface temperatures: the columns had the highest psi values but presented no risk of moisture damage.

Colour-coded 3D thermal simulation of a square concrete column rising from an insulated floor slab, warm red above and cold blue below.
3D thermal bridge model of a concrete column passing through the insulated floor above the unheated commercial unit below. Click to enlarge.
Bright living room with a white structural column, a grey sofa, a green-painted lower wall and a large window.
One of the concrete columns in the finished living room.

Airtightness: tested once, passed first time

The existing plaster, repaired where needed, forms the airtight layer, and every service penetration was sealed before the linings closed. A blower-door test is not mandatory for EnerPHit Unit certification, but here it was built into site management from the start. The blower-door test served as both quality control on site and the final check: no further tests were needed.

The test measured n50 = 0.85/h at 50 Pa, for an internal volume of 214.3 m³, with an envelope air permeability q50 of 0.78 m³/(h·m²), at the first attempt. That result came from rigorous detailing and site control by Martin Johnson, with a team new to Passive House.

Close-up of a corrugated cable conduit coming out of a white plastered wall, sealed with a dark airtight compound.
A service penetration sealed with airtight compound before the wall lining was closed.
Red blower-door fan fitted in a doorway, with a laptop and pressure gauge on a tripod beside it.
The blower-door test, with the fan mounted in the entrance door.

Ventilation, heating and hot water

A compact, balanced mechanical ventilation unit with 77% effective heat recovery supplies fresh air to every room, which matters as much for indoor air quality as for energy. The ductwork runs in lowered ceilings, keeping the living spaces clear.

With the envelope doing the work, heating is limited to a 1 kW electric post-heater in the supply air and a 500 W towel rail in the bathroom.

Domestic hot water comes from a compact, ducted air-source heat pump, which allowed the gas connection to be removed.

Summer comfort

The owners report that summer comfort is also very good. Natural night-time cross-ventilation cools the thermal mass inside the flat, and external Venetian blinds shade the windows during the day.

Certification allows a frequency of overheating of up to 10%; the recommended target is 2%, and the project meets it.

White cylindrical hot-water heat pump in a utility cupboard, with insulated ducts running above it.
The compact air-source heat pump for domestic hot water, with the ventilation ductwork above.
Small bedroom with an oak floor, a green-painted lower wall, a white desk and a timber-framed window, with sunlight on the floor.
A bedroom in the finished flat, with one of the new timber-framed windows.

The results

IndicatorResult
Heating demand23 kWh/(m²a)
Primary Energy Renewable (PER)63 kWh/(m²a)
Frequency of overheating (> 25 °C)2%
Frequency of excessively high humidity15%
Airtightness, n50 (measured)0.85/h
Treated floor area88 m²

After a year and a half of occupation, the flat stays at about 21 °C in winter, the air quality is excellent, and the electricity bill is around €900 a year.

Open-plan kitchen with timber units and an island, oak floor and large timber-framed windows onto a garden.
The kitchen and dining area of Etxea Laura eta Martin after the retrofit. Photo: Martin Johnson.

Living in it

The owners moved in before the flat was finished. In Martin’s words:

In hindsight, the time pressure and constraints provided the focus required to ensure the important aspects of the build had clear and achievable targets. Collaboration was paramount, and clear communication was key to avoid abortive and repeat work. No one on the team had experience in Passivhaus, yet everyone was willing to listen, understand what was required and work towards the target.

We moved in with no floor finishes, unpainted walls, hanging light bulbs and no internal doors. Still, we had an air test certificate, a working ventilation system, no reliance on gas, hot water from a compact air-source heat pump, a lovely woody smell from all that wood-fibre insulation, exceptional air quality and internal comfort, and a soon-to-be-certified EnerPHit Unit.

We are still missing the odd skirting board. En casa de herrero, cuchillo de palo: the blacksmith’s house has wooden knives!

— Martin Johnson, architect and developer
Two photos side by side: a dated bathroom with grey marble-effect tiles, and the new bathroom with dark green tiles, a glass shower screen and a wall-hung toilet.
The bathroom before (left) and after (right) the retrofit.

A workflow that can scale

Speed on this project depended less on novel products than on integrating design, sequencing and quality assurance. The approach can be packaged for other occupied apartment buildings:

  1. Survey the shared constraints first: shunts, drains, pipes and structure that belong to the building, not the flat.
  2. Minimise wet work, so trades can follow each other quickly.
  3. Use low-impact internal systems that fit the space available.
  4. Resolve every penetration before the linings close.
  5. Make airtightness testing part of site management, not an afterthought.

The principal lesson is that simplicity is an outcome of rigorous coordination, not reduced performance.

What this project shows

A deep energy retrofit does not have to wait for a whole building to agree. Working from the inside, with simple dry build-ups, careful thermal bridge design and airtightness treated as a site discipline, a single flat can reach EnerPHit quality with a team that is new to Passive House.

It also shows that certification is about more than an energy figure. Thermal bridges and moisture risk, summer overheating and ventilation were all part of the review, just as they were on larger retrofits such as Casa SG Magí in Sitges and Hotel Marcel in New Haven. Praxis is also a qualified airtightness testing laboratory, for projects that want the blower-door test on their side from the start.

The short version

  • 23 kWh/(m²a) heating demand and 63 kWh/(m²a) PER, reached entirely from inside an 88 m² flat
  • No work on the façade and no need to wait for the neighbours
  • Three months to design and three months to build, with natural, largely bio-based materials
  • n50 = 0.85/h measured at the first attempt, with a contractor new to Passive House
  • Heating limited to a 1 kW post-heater and a 500 W towel rail, and the gas connection removed
  • About 21 °C in winter, very good summer comfort and around €900 of electricity a year

One flat in an ordinary 1960s block has shown that EnerPHit does not have to wait for the whole building.

Do you have a flat and want a deep energy retrofit? Tell us about it.

Etxea Laura eta Martin is certified EnerPHit Unit. Praxis Resilient Buildings carried out the Passivhaus EnerPHit Unit certification.

A 1952 town hall, rebuilt in eight and a half months

Llinars del Vallès rebuilt its 1952 town hall in 8.5 months, co-funded by NextGenerationEU. Catalonia’s first EnerPHit certified office building.

A 1952 town hall, rebuilt in eight and a half months

In January 2024, Llinars del Vallès started work on its town hall with a deadline it could not move. The building on the Plaça de la Vila dated from 1952, around 955 m² over three floors, and it had the problems you would expect: solid walls with no insulation, original windows, and four separate citizen service desks spread through a plan that had grown by accretion. By 16 September the works had to be finished, or the European funding paying for three quarters of them would be lost.

It got finished. The building is now the first administrative building in Catalonia certified to the Passivhaus EnerPHit standard, in the Plus class.

A 1952 town hall, rebuilt in eight and a half months
Side by side comparison of the town hall facade before and after the retrofit
The same elevation before and after: bare masonry and original windows, then an insulated envelope.

A fixed budget and a fixed date

The works cost 804,650 € including VAT, about 842 € per square metre. Of that, 601,750 € came from the Recovery, Transformation and Resilience Plan, funded by the European Union through NextGenerationEU, and 202,900 € from the council’s own budget. The grant set both the ceiling and the calendar: four months to produce the design, eight and a half to build.

That matters more than it sounds. A deep energy retrofit is usually sold as something slow and disruptive. This one was programmed like any other municipal contract, in a building that stayed in use.

Wrapping a building that was never designed to be wrapped

The façades were insulated from the outside with Ytong Multipor mineral insulation board — 120 mm on the main brick elevations, 80 to 100 mm where the geometry was tighter — taking the walls from bare masonry to between 0.24 and 0.41 W/(m²K). The flat roofs received 80 mm of XPS over 40 mm already there; the pitched roofs 100 mm, giving 0.26 to 0.28 W/(m²K). A liquid applied membrane was taken around the whole envelope behind the insulation to form a continuous airtight layer.

Close up of mineral insulation board being fixed over a liquid applied membrane at the foot of a wall
Mineral insulation board going on over the continuous airtight membrane at the base of the wall.

Insulating from the outside rather than the inside was the decision that made the rest possible. It keeps the existing masonry inside the warm envelope, where its weight steadies the internal temperature through a Vallès summer. It leaves the junctions accessible, so they can be resolved rather than worked around. And it costs the council nothing in floor area, which in a building where four service desks were being consolidated into one mattered as much as the energy.

Every window was replaced with triple glazed, low-e, argon filled Smartwin timber-aluminium units made by Ventanas Gardea, installed at 1.27 W/(m²K) including frames and fixing. The insulation was returned into the reveals, so the frames sit within the insulation line rather than at the edge of it.

Diagram of the floor to wall junction showing continuous insulation and the calculated thermal bridge value
The slab-to-wall junction, with the insulation line carried through. Linear thermal bridge coefficient 0.096 W/(m·K).

The junctions decide the result

Insulation thickness is the easy part. What determines whether a retrofit performs is what happens where elements meet, and in a 1950s building those junctions were never detailed for it.

Two-dimensional thermal bridge calculations were made to ISO 10211 for the critical details. At the slab to wall junction the linear thermal bridge coefficient came out at 0.096 W/(m·K), with a temperature factor of 0.766 against a required minimum of 0.31 for this climate. The minimum internal surface temperature in that detail is 15.3 °C when it is freezing outside, which is what keeps condensation and mould off it.

Checked rather than assumed

A certified building is not one where the design intent was good. It is one where every number was traced back to something real before it was accepted.

The energy model is rebuilt against evidence: conductivity values taken from the data sheets for the boards actually delivered to site, window performance from the installed units including frames and fixings rather than the glass alone, heat recovery from the ventilation unit’s own component certificate rather than a brochure figure, areas checked against site photographs. Where a value cannot be evidenced, it does not go into the model.

Then the two things that cannot be modelled are measured. Airtightness is tested on the finished building, not declared. Ventilation flow rates are commissioned and measured room by room, because a heat recovery unit that is 84% efficient on paper recovers nothing useful if the system is unbalanced.

That is the difference between a building that should perform and one that does.

Every gap in the building, added up

On 15 October 2024 the completed building was tested with a blower door. Air is pushed in and drawn out at a range of pressures and the leakage is measured against the internal volume, here 2,346 m³, inside an envelope of 1,428 m².

The result was n50 = 0.88 air changes per hour, measured, against a limit of 1.04 for this project. That is 2,065 m³/h of air leaking at 50 pascals.

The number that makes it real is the equivalent leakage area. Add every crack, service penetration and badly closing joint in the building together and they come to 0.0629 m²: a single square hole about 25 cm by 25 cm, in a 1,428 m² envelope that was built in 1952.

Graph of the measured air change rate against the certification limit, with the equivalent leakage area shown to scale
The measured airtightness result against the limit, and the leakage area it represents.
Mechanical ventilation unit with large insulated ducts on a flat roof during installation
The ventilation unit and its ductwork being installed on the roof.
Office workspace with timber framed triple glazed windows and desks along a wall
An office on the upper floor: daylight, triple glazing and continuous filtered air.

Air, heat and cold

Ventilation is a Zehnder Carma unit on the roof, Passivhaus certified, recovering 84% of the heat from the air it extracts. It runs continuously and filters what it brings in, which in an office with a public counter is as much about air quality as about energy.

It was commissioned in March 2025 and measured room by room: 2,351 m³/h supplied against 2,330 designed, and 2,357 m³/h extracted. Balanced to within one percent of the design, which is where heat recovery either works or does not.

Heating comes from the municipal biomass district network through wall mounted fan coils. The same fan coils provide cooling in summer from a chiller on the roof. A Loxone system monitors energy use and indoor air quality in real time.

Solar, and what it covers

There is 19.3 kWp of photovoltaic on the roof: 13.6 kWp installed as part of the works, alongside 5.7 kWp already there. Together they produce about 25,300 kWh a year against a building demand of around 36,300 kWh, roughly 70% of everything the building uses, in final energy. In the certification’s terms, the building generates 67 kWh/(m²·a) per square metre of building footprint of renewable energy against a renewable primary energy demand of 43 kWh/(m²·a), per square metre of treated floor area, which is what earns the Plus class.

Photovoltaic panels mounted on the roof of the town hall
The photovoltaic array on the roof, 19.3 kWp in total.

What the certificate says

Measured against a treated floor area of 761 m², and against the EnerPHit criteria for this climate:

Heating demand came in at 18 kWh/(m²·a) against a limit of 20. Cooling and dehumidification at 4 against 15. Excessive humidity occurs 4% of the year against a limit of 10%. Airtightness, 0.88 against 1.04.

Not one of them is a near miss, and all of them are on a building from 1952.

Graph comparing the certified heating demand, cooling demand, humidity frequency and airtightness against their limits
The certified results against the EnerPHit criteria for this climate.
The town hall seen from the public square with trees and planters in front
The building back in use on the square it has stood on since 1952.

The point

A municipality with a capped budget and a hard deadline took a post-war office building and got a certified deep retrofit out of it in eight and a half months. The people working there have stable temperatures, filtered air and daylight; the council has an asset worth more and a running cost a fraction of what it was.

There are a great many town halls like this one.

Short version

1952 town hall, around 955 m², retrofitted in eight and a half months for 804,650 € with NextGenerationEU funding. 120 mm external mineral insulation, triple glazing, n50 = 0.88, 84% heat recovery, 19.3 kWp of solar. Heating demand 18 kWh/(m²·a). Catalonia’s first EnerPHit certified administrative building, Plus class.

Praxis Resilient Buildings carried out the Passivhaus certification and the airtightness testing on this project.

Project page: Ajuntament Llinars del Vallès, Catalonia, EnerPHit Plus retrofit

How to Renew Your Passivhaus Designer/Consultant or Tradesperson Certificate (2026 Guide)

How to renew your Passivhaus certificate as a Designer/Consultant or Tradesperson: both routes, 100/30 credit points, fees and the 2025 PHI changes.

How to Renew Your Passivhaus Designer/Consultant or Tradesperson Certificate (2026 Guide)

Passing the Certified Passivhaus Designer/Consultant or Tradesperson exam is a real achievement, but the certificate only lasts five years. If you need to renew your Passivhaus certificate, there is good news: the Passive House Institute (PHI) made renewal considerably easier in 2025. The catch is that much of the advice still online describes the old rules.

This guide explains how renewal works today for both qualifications. It is based on PHI’s current Regulations for Continuing Education, valid from 1 January 2025, and on PHI’s own renewal pages.

Title graphic for a guide to renewing Passivhaus Designer, Consultant and Tradesperson certificates, showing 5 years validity, 100 CP and 30 CP
Diagram of the two renewal routes for Passivhaus Designer/Consultant and Tradesperson certificates: project documentation or credit points

Passivhaus certificate renewal at a glance 

  • Both certificates are valid for five years and can be renewed as many times as you like.
  • Designers/Consultants renew with a certified building or 100 credit points (CP).
  • Tradespeople renew by documenting their own work or with 30 CP.
  • One CP equals one 45-minute learning unit.
  • You cannot renew by retaking the exam.
  • Praxis is an accredited assessing body for certificate renewals. Contact us here for a fee quote

How long is a Passivhaus certificate valid? 

Both certificates are valid for five years, and you can renew them as often as you like. If yours expires, your entry in PHI’s public directory of certified professionals is deactivated and deleted six months later. That listing matters: clients find you there, and some tenders ask for proof of a valid certificate.

You cannot renew by retaking the exam, even if your certificate expired long ago. The exam is only for your first qualification. After that, there are two ways to renew: by documenting real project work, or by collecting continuing education credit points.

How to renew as a Passivhaus Designer or Consultant 

Route 1: document a certified building 

You can renew by submitting documentation for a building where you were responsible for the energy-relevant design, including the PHPP. The building must:

  • be completed and in use;
  • be certified as a Passive House, EnerPHit retrofit or PHI Low Energy Building (EnerPHit pre-certification for a staged retrofit also counts);
  • be listed in the Passive House Database.

You can submit to a PHI-accredited assessing body such as Praxis, in English, Spanish, Catalan, French and German, plus a summary in English. You will need:

  • the application form;
  • a detailed building description using PHI’s template;
  • the unprotected PHPP file;
  • a copy of the building certificate;
  • the building’s database ID;
  • if you weren’t the lead designer, a signed statement from the designer confirming your role.

Normally only one person can use a given building. For complex buildings over 4,000 m², two people may each submit if they were responsible for different parts, such as the envelope and the building services.

Route 2: collect 100 Passive House credit points 

If you don’t have a certified building in the pipeline, you can renew with 100 CP. One CP equals one 45-minute learning unit, with a maximum of 8 CP per day. Courses and events must focus on highly energy-efficient construction and the Passivhaus Standard.

Comparison table of the old 2016 and current 2025 Passivhaus Designer/Consultant renewal rules

What changed in 2025 

If you last read up on renewal a few years ago, several important rules are different now:

  • You keep the Designer title. Renewing through credit points no longer downgrades a Designer to Consultant.
  • All your points can come from one source. The old caps on how many points could come from each category have been removed. Courses alone, events alone or teaching alone are all fine.
  • Teaching counts at the same rate as attending.
  • Extra points can be carried forward to your next renewal.
  • Expired certificates can still be renewed with points. All 100 CP must be less than five years old when you apply.

PHI’s Designer/Consultant certificate page sets out the current process in full.

How to renew as a Passivhaus Tradesperson 

Route 1: document your own work 

Tradespeople can renew by documenting their own work on a highly energy-efficient building. Unlike the Designer route, the building does not have to be a certified Passive House. Your work just has to meet the energy criteria for your trade and climate zone. The process has three steps:

  • Find your climate zone on PHI’s climate zone map.
  • Download the criteria for your trade. PHI publishes separate requirements for shell construction, carpentry, roofing and plastering insulation, window installation, ventilation, heating and hot water, and airtight electrical installations.
  • Submit the renewal application, your work documentation (using PHI’s template) and a short declaration from the client, designer or business owner confirming that you did the work yourself. These go to a PHI-accredited assessing body such as Praxis, with a summary in English.

Route 2: collect 30 credit points 

Alternatively, collect 30 CP. One 45-minute learning unit equals one CP, and you can earn no more than 20 CP in any one area (teaching, events or advanced training courses). Full details are on PHI’s Tradesperson certificate page.

How to log your Passive House credit points 

PHI now manages credit points online, and renewal is much easier if you log them as you go. PHI’s credit point FAQ shows the process with screenshots.

  • Step 1: Log in to your Passive House database account and open Exams & Certificates.
  • Step 2: Click Add accredited training, then search for the event by name or ID.
  • Step 3: Upload your proof of attendance and click Add to attended.
  • Step 4: PHI checks your proof before the points are credited.
  • Step 5: When you reach 100 CP (Designer/Consultant) or 30 CP (Tradesperson), the Renew certificate button becomes active.
  • Step 6: Click it. PHI sends an invoice, and once it’s paid, you receive your renewed certificate by email.
Six-step diagram showing how to log Passivhaus credit points and renew a certificate in the Passive House Institute online portal

How much does it cost to renew? 

Praxis is an accredited assessing body for certificate renewals, for Designers and Tradespersons looking to renew their certificates through project and work documentation. Contact us here for a fee quote.

A Praxis Resilient Buildings trainer presenting at a Passivhaus training session in Barcelona

Where to find Passivhaus credit points 

  • PHI’s directories of accredited events for Designers/Consultants and for Tradespeople. Every event has an ID number, and you’ll need it to claim.
  • Conferences give the most points in one go. The International Passive House Conference typically awards around 36 CP. National conferences such as the UK Passivhaus Conference and the AECB Conference typically award around 10–16 CP.
  • iPHA webinars are worth 2 CP each, including the recordings. The same material viewed on Passipedia doesn’t earn points.
  • Accredited training providers and national affiliates offer courses, masterclasses and webinars, many of them online. Our Passivhaus courses at Praxis Resilient Buildings are validated by PHI, and we also run in-company training for teams.
  • If a relevant event isn’t listed, ask the organiser to submit it to PHI using the event accreditation form. This can be done retrospectively.

Beware of outdated renewal advice 

Several guides still online describe the 2016 rules. Treat the following claims as out of date:

  • that no more than 70 of your 100 points can come from one category;
  • that points can’t be carried forward;
  • that Designers can only keep their title by documenting a building;

If in doubt, contact us here.

Five tips for a stress-free renewal 

  • Start straight after you qualify. Aiming for about 20 CP a year for Designers, or 6 CP a year for Tradespeople, keeps renewal stress-free.
  • Log every event as soon as you’ve attended it and keep your attendance certificates.
  • Check that an event is accredited, and note its ID, before you book.
  • Don’t let it lapse. Expired certificates can still be renewed, but you lose your directory listing and can’t use the seal in the meantime.
  • Keep it valid if you want add-on seals. Additional qualifications such as PHPP Expert, Retrofit or Construction Verifier require a valid main certificate.
Bar and line chart showing an example five-year plan to collect 100 Passivhaus credit points from webinars, online courses and conferences

Praxis Resilient Buildings is an engineering and consultancy practice in Barcelona, and an accredited Passivhaus training company recognised by the Passive House Institute and Plataforma PEP. This guide reflects PHI’s rules as of September 2026; always check the latest regulations with PHI before applying. Sources: Passive House Institute (certificate pages, FAQ, Regulations for Continuing Education 2025, fee schedules 2025), Coaction, The Passive House Network, Passivhaus Trust, Passive House Canada.

One Year in a Passivhaus Plus Home: 11,929 kWh Generated and €332 in Energy Bills 

First-year measured data from Can Naiades, a Passivhaus Plus home near Barcelona: 11,929 kWh generated, 85% self-sufficient, €332 of electricity bills.

One Year in a Passivhaus Plus Home: 11,929 kWh Generated and €332 in Energy Bills 

I’ve learnt that the first few months after moving into a house you have built yourself are probably more stressful than the whole construction process. There are bills still to pay and no money in the account. Your business has suffered because you gave so much of your time to the project. Aches and pains surface in odd parts of your body from too many hours hunched over a cost-control spreadsheet.

And then there is a point where you close the spreadsheet, decide never to open it again, and actually begin enjoying the wonders of living in a decent house — one that is genuinely comfortable, has great air quality, and is remarkably cheap to run.

That was a year ago. We now have twelve full months of measured data from Can Naiades, our certified Passivhaus Plus home in Sant Julià d’Alfou, 40 km north-east of Barcelona. This is what the first year in a Passivhaus Plus home actually looks like, in kilowatt hours and in euros.

Can Naiades, vivienda certificada Passivhaus Plus cerca de Barcelona, fotografiada al atardecer
Can Naiades at dusk. The house was certified Passivhaus Plus and Near Zero CO₂ in 2026. Photo: Pol Viladoms. 
Espacio de doble altura en Can Naiades con puertas correderas de triple vidrio orientadas al sur abiertas al jardín
The double-height living space opens onto the terrace. Solar gains through the south glazing cover 79% of the heating demand. 

A quick recap of the house 

Can Naiades is a two-storey, four-bedroom family home of 127 m² treated floor area, built on a prefabricated lightweight timber frame. The envelope is insulated with recycled glass wool — 250 mm in the walls and 350 mm in the roof — with triple-glazed timber-aluminium windows at Uw 0.81 W/(m²K) as installed, and an airtightness of 0.44 air changes per hour at 50 Pa. Every window has an external venetian blind. If you want the full build story, we set it out in the fifteen steps we took towards a comfortable, healthy, resilient and efficient home.

There is no conventional central heating system. A heat pump with a single ducted split unit, sized for the cooling load, also provides occasional heating; the rest is handled by small towel radiators in the bathrooms and an underfloor loop in the ground-floor bathroom. Fresh air comes from a balanced mechanical ventilation unit with heat and moisture recovery, running continuously. On the roof sit 21 photovoltaic panels totalling 8.5 kWp, paired with a 13.8 kWh battery.

Here is the finished house in a minute, before we get to the numbers.

How we calibrated the PHPP model 

Comparing measured data against a design model is only meaningful if the model has been told the truth about the year that actually happened. So before making any comparison, we calibrated the PHPP certification model in two ways.

First, we replaced the standard climate data set with outdoor air temperature and relative humidity recorded at a local meteorological station over the monitoring period. Second, we adjusted the occupancy assumptions to match the household as it really is — three adults and two young children — rather than the standard occupancy the certification method assumes.

That matters. Without those two corrections you are comparing a real house in a real year against a generic house in an average year, and any agreement — or disagreement — between the two tells you very little.

Bar chart comparing PHPP predicted and measured annual PV generation and energy consumption at Can Naiades
Annual PV generation and consumption, PHPP prediction against measured data, September 2025 to August 2026.

What the house generated, and what it used 

Over the twelve months from 1 September 2025 to 31 August 2026, the photovoltaic array generated 11,929 kWh. Total consumption across the same period was 7,835 kWh, of which 898 kWh went into charging a plug-in hybrid car — roughly 4,000 km of electric running. Strip the car out and the house itself used 6,937 kWh.

So the house generated 52% more electricity than everything in it consumed, car included. Against the building alone, generation was 72% higher than consumption.

The agreement with the calibrated model is the part we find most satisfying. PHPP predicted 11,139 kWh of generation; the array delivered 11,929 kWh, 7% ahead. PHPP predicted 7,052 kWh of household consumption; the meters recorded 6,937 kWh, 1.6% below. For a whole-building energy model to land within a couple of per cent of reality over a full year is about as good as this work gets.

Of the 11,929 kWh generated, 6,697 kWh was used directly in the house — a self-consumption rate of 56%, helped considerably by the battery. The remaining 4,964 kWh went to the grid. Over the year the house drew just 1,149 kWh back from the grid, which means 85% of everything it consumed was covered on site, and it exported 3,815 kWh more than it imported. Averaged out, that is 32.7 kWh generated and 21.5 kWh consumed per day, with only 3.1 kWh a day coming off the grid.

Consumption, month by month 

The annual totals agree almost exactly, but the monthly pattern varies. From December to May the house used more than the model predicted, most noticeably in January at around 30% above. From June to September the reverse held, with measured consumption comfortably below the model — particularly in July and August, where PHPP expected over a megawatt hour a month and the house used considerably less. Our first summer article covers how the house is kept cool: the blinds, natural night ventilation where possible, and a small amount of active cooling from the single split unit.

So PHPP overestimated our summer cooling energy and underestimated our winter and shoulder-season electricity use, and the two discrepancies very nearly cancel out across the year. That is consistent with the caveats in EN ISO 13790 — since superseded by EN ISO 52016 — on which PHPP’s monthly energy demand calculations are based: the monthly method is reliable for the annual total but not necessarily for individual months, and relative errors can be large at the start and end of the heating or cooling season.

Bar chart of monthly PHPP predicted versus measured energy consumption at Can Naiades
Monthly energy consumption, PHPP prediction against measured data, excluding car charging.
Bar chart of monthly PHPP predicted versus measured solar PV generation at Can Naiades
Monthly PV generation, PHPP prediction against measured output.

Solar generation, month by month 

The array beat the model in nine months out of twelve, with the largest gains in April and June. Three came in below prediction: January and December, both marginal, and September, where measured output of 650 kWh fell well short of the 990 kWh predicted. September stands out against every other month, explained by cloudier weather than usual and less solar radiation.

The energy bills 

Across twelve months the total electricity bill for the house came to €332 — an average of €28 a month. That is the whole bill: heating, cooling, hot water, ventilation, lighting, appliances and PHEV car charging, for a household of three adults and two young children.

The shape of it matters as much as the total. June, July and August cost nothing at all, because generation and export credits covered everything the house drew. April and May came in at €2 and €1. The bills only become visible in the depths of winter, peaking at €95 in January and €94 in December, when generation falls to roughly a third of its summer level and the house draws more from the grid. Even then, a €95 winter electricity bill for an all-electric four-bedroom house is not a number most people are used to seeing.

Bar chart of monthly electricity bills at Can Naiades, showing three months at zero euros
Monthly electricity bill across the year. Three summer months came in at zero.
Vista aérea de Can Naiades con la instalación fotovoltaica en cubierta y el Montseny al fondo
The 8.5 kWp rooftop array, 21 panels, paired with a 13.8 kWh battery. 
Cuarto técnico de Can Naiades con el equipo de ventilación con recuperación de calor y la bomba de calor
The plant room: balanced ventilation with heat and moisture recovery, and a high-efficiency heat pump. No boiler, no combustion.

What a year of living here has taught us 

Three things stand out.

The first is that a well-calibrated model is worth the effort. Landing within 2% on consumption over a full year is not luck; it is what happens when the climate data and the occupancy reflect reality. It also means we can now trust the model when it tells us something about a future year, or about a design change we are considering.

The second is that the building fabric does the heavy lifting, and the systems stay small. There is no boiler and no combustion anywhere in the house. There is one split unit, a couple of towel rails, and a ventilation unit that runs quietly in the background — and how the ventilation unit has actually performed is a story in its own right. The comfort does not come from the kit; it comes from insulation, airtightness, glazing and shading getting the conditions close to right before any system is asked to do anything.

The third is that the numbers only tell part of it. Stable temperatures, no draughts, no radiators taking up wall space, quiet rooms and air that stays fresh are things you notice daily and stop being able to measure. We wrote about that in more detail after our first winter.

The short version 

  • 11,929 kWh generated over the year, against 7,835 kWh consumed including PHEV charging — 52% more produced than used
  • 85% of all consumption covered on site by solar PV and battery storage, with just 1,149 kWh drawn from the grid
  • 3,815 kWh net exported to the grid
  • €332 of electricity for the whole year, averaging €28 a month, with three months at zero
  • Measured consumption within 1.6% of the calibrated PHPP prediction, and generation 7% ahead of it

A Passivhaus Plus home is not a theoretical proposition. This one has now run for a year, and the meters agree with the design.

Can Naiades is certified Passivhaus Plus and Near Zero CO₂. Praxis Resilient Buildings delivered the Passivhaus design, site supervision, preliminary Blower Door testing, thermal bridge calculations, dynamic hygrothermal modelling with WUFI and the HVAC system design.

Vista exterior de Can Naiades al atardecer con los interiores iluminados, un año después de su finalización
Can Naiades, one year on. 

Cooling the World Cup: USA vs Qatar

Only three U.S. World Cup venues can genuinely be described as actively cooled match stadiums: Atlanta, Dallas and Houston.

Cooling the World Cup: USA vs Qatar

Two approaches to conditioning large football stadiums in warm climates.

Only three U.S. World Cup venues can genuinely be described as actively cooled match stadiums: Atlanta, Dallas and Houston. The key point is not concourse air-conditioning, but the ability—when the retractable roof is closed—to condition the spectator bowl and pitch as one large indoor volume. 

Cooling the World Cup: USA vs Qatar

This is effective, but not subtle. The U.S. strategy is to enclose first and cool second. Qatar 2022 used a different logic: architectural form, air movement and local supply to create cooled microclimates around spectators and the pitch. The real comparison is therefore not whether cooling works, but how efficiently, evenly and robustly it delivers comfort, using the least possible energy. 

Is active cooling necessary in football stadiums? 

In June and July, outdoor temperatures in Atlanta, north Texas and Houston can exceed 35°C / 95°F. Atlanta and Dallas have similar absolute humidity, around 17 g/m³, while Houston is closer to 20 g/m³, meaning roughly 20% more moisture in the air. Houston is therefore the most latent-load driven case: the plant must remove water vapour as well as heat. 

For players, high wet-bulb conditions reduce evaporative heat loss, increase cardiovascular strain and can reduce high-intensity running. For spectators, long dwell times, queuing, alcohol consumption and limited personal control turn heat into a crowd-safety issue. Cooling is therefore part of the event strategy, not a luxury. The weakness is that it depends on treating each stadium as a sealed building: roof open, doors open, uncontrolled solar gains or leakage at the retractable roof perimeter all make the cooling task less elegant and more energy intensive. 

Estadio de Atlanta

Atlanta Stadium: integrated, but still a huge, conditioned volume 

Atlanta is the most integrated of the three. Its retractable roof closes the bowl, and the stadium combines daylighting, automated controls, LED lighting and a wider sustainability narrative. It is closest to a whole-building proposition rather than simply a stadium with a very large chiller plant. 

The cooling principle is still conventional: reduce air exchange, enclose the volume, and condition it with high-capacity HVAC. This should give stable operative temperatures once the roof is closed. The limitation is the envelope: a large roof aperture, translucent roof elements and a very high internal volume all carry thermal penalties. It may be efficient by U.S. mega-venue standards, but that is a low bar compared with reducing the conditioned volume or supplying comfort locally. 

Dallas Stadium: effective comfort, blunt energy logic 

Dallas is the clearest expression of the U.S. model: close the roof and operate the stadium as a giant air-conditioned arena. Reported closed-roof conditions are around 22–24°C / 72–75°F even when outdoor temperatures are close to 35°C / 95°F and perceived outdoor conditions approach 41°C / 106°F. Technically, that is a successful comfort outcome.  The cost is energy intensity. Published estimates put Dallas close to 100,000 kWh per match for air-conditioning. In U.S. energy terms, that is about 341 million BTU of electrical input per match before considering plant efficiency and distribution losses. Even allowing for uncertainty, the order of magnitude is telling: comfort is delivered primarily by plant capacity, not by climatic intelligence. The system works, but success is bought mechanically. 

Estadio de Dallas
Estadio de Houston: la advertencia más clara sobre la envolvente

Houston Stadium: the clearest envelope warning 

Houston is the hardest case because heat and humidity combine. With the roof closed, the stadium can act as a conditioned bowl and protect spectators from direct sun and rain. But it also shows why ‘retractable roof’ and ‘thermal envelope’ are not the same thing. The stadium performs well only when the roof and major openings are treated as a serious thermal boundary.  When the roof is open, solar exposure is uneven: south and west areas are generally more protected, while north and east areas are more exposed. This matters because mean radiant temperature can rise even if the air temperature is acceptable. In those conditions, internal shading and strict roof/opening control become part of the cooling strategy, not operational footnotes. Air leakage, roof perimeter gaps, large volumes and solar penetration all reduce the effectiveness of mechanical cooling.

Qatar 2022: targeted microclimate rather than cooled void 

Qatar’s strategy was fundamentally different in the 2022 world cup. It did not attempt to cool an entire stadium void. The principle was spot cooling: supply cool air where people and players actually are, through grilles in the stands and larger pitch-side nozzles. Stadium form, insulation, air recirculation, filtration, wind-tunnel testing and CFD were used to contain a cooled microclimate within a semi-open condition. 

This is a more interesting comfort strategy because it starts from the occupied zone: the spectator’s ankles, the occupied tier, the player and the pitch boundary layer. It also recognises that comfort depends on radiant temperature and air movement, not only dry-bulb temperature. The U.S. approach is simpler and probably more robust operationally: close the roof, set a temperature, run the plant. But it cools a very large volume whether or not each cubic metre contributes to comfort. Qatar’s approach was not free of energy or carbon questions, but conceptually its efficiency argument is stronger because comfort was targeted rather than volume-wide. 

Qatar 2022: microclima dirigido en lugar de enfriar el vacío
Qatar 2022: microclima dirigido en lugar de enfriar el vacío

What monitored data is available? 

The evidence base is thinner than it should be. For the U.S. venues, the best public energy figures are estimates rather than confirmed BMS or utility-meter data: approximately 99,925 kWh per match for Dallas, 97,344 kWh for Houston and 96,020 kWh for Atlanta. Dallas also has a reported internal range of 22–24°C / 72–75°F, but without relative humidity, air speed, radiant temperature or sensor locations, this is not a full comfort dataset. 

For Qatar, the public evidence is technically richer—CFD, wind-tunnel work, targeted supply, air recirculation and reported target conditions around 18–24°C / 64–75°F—but still not equivalent to transparent post-occupancy monitoring. One CFD-based study reported acceptable comfort under external conditions up to 48°C / 118°F and 70% relative humidity, with many zones maintaining thermal neutrality even when cooling load was reduced by about 50%. That supports the design logic, but it remains modelled evidence, not match monitoring. 

A rigorous comparison—kWh per spectator-hour, kWh per comfort-hour, or WBGT reduction per kWh—is therefore not possible from public sources. The available evidence suggests that U.S. closed-roof cooling works, while Qatar’s strategy is conceptually more energy efficient. But neither case has yet published enough monitored data to prove performance transparently. 

Lessons learned 

First, enclosure works only if it is treated seriously. A retractable roof becomes a thermal envelope only when airtightness, solar control, perimeter detailing and operational discipline are adequate. 

Second, comfort must be measured at the occupant, not the thermostat. Air temperature alone is insufficient; radiant temperature, humidity, air speed, stratification and crowd density all matter. 

Third, energy efficiency depends on reducing load before increasing plant size. Qatar’s hierarchy—shade, shape, contain, supply locally, recirculate, then cool—is better environmental design. The U.S. model starts further downstream: close the lid and cool the room. 

The conclusion is simple: Atlanta, Dallas and Houston can host safe, comfortable matches, but they should not be mistaken for low-energy precedents. The best cooling strategy is not a bigger chiller. It is a better solar control, better scheduling (i.e. hosting games at cooler hours of the day) and a better envelope.

Hotel Marcel New Haven: Inside America’s Leading Passive House Hotel at PHN Conference 2026

Discover Hotel Marcel in New Haven, the only Passive House-certified hotel in the US and host of the PHN Conference 2026. A first-hand look at comfort, retrofit design, energy systems, and sustainable hospitality.

Hotel Marcel New Haven: Inside America’s Leading Passive House Hotel at PHN Conference 2026

A first-hand stay at the Passive House Network USA’s 2026 Conference venue.

By Oliver Style, Praxis CEO.

Hotel Marcel New Haven: Inside America’s Leading Passive House Hotel at PHN Conference 2026

Hotel Marcel, New Haven.

Hosting the Passive House Network Conference 2026.

Intro

Hotel Marcel in New Haven is far more than a design hotel: it is one of the most important sustainable retrofit projects in the hospitality sector. Formerly the Armstrong Rubber Company Building, later known as the Pirelli Tire Building, this iconic Brutalist structure was designed by modernist architect Marcel Breuer. After sitting abandoned and unoccupied for nearly two decades, it was purchased by IKEA and partially demolished before being sold on again. In 2019, Bruce Becker—architect, developer, and founder of Becker + Becker—acquired the building and surrounding property from IKEA for $1.2 million. Under the terms of the deal, Becker agreed to remove the remaining asbestos, meet a series of sustainability conditions, and purchase furniture from IKEA. Becker + Becker then set out to transform the building into a carbon-neutral, fully electric hotel that could rely on its own energy generation. The ambition was bold: to create the first Passive House-certified hotel in the United States. Today, Hotel Marcel stands as the world’s first Passivhaus-retrofitted Brutalist hotel and, during the first week of June 2026, it also served as the venue for the Passive House Network USA’s 2026 Conference, where I had the honour of presenting the Mirador de Gracia project: “Certified Senior Care Housing Comes to Catalonia”.

Sensations

One of the most impressive aspects of staying at Hotel Marcel is how clearly you can feel the benefits of high-performance design. The hotel sits immediately next to a major highway, yet once inside it is astonishingly quiet and restful. Triple-glazed windows, excellent airtightness, and—as far as is realistically possible in a retrofit with internal thermal insulation—continuous insulation create a calm, protected indoor environment that feels completely detached from the traffic outside. I stayed there in the first week of June 2026, at the start of summer: the hotel remained exceptionally comfortable, and I had the air conditioning turned off for most of my stay. The indoor air quality was equally noticeable. Unlike many conventional hotels, there was no sense of stale or stuffy air in the morning. Instead, the rooms felt fresh, light, and airy—exactly the kind of comfort Passive House projects promise, but which is rarely so tangible to the guest.

Numbers

Hotel Marcel also makes a strong business case for Passive House in hospitality. During the conference, Bruce Becker explained that Passive House certification has added approximately USD $6 million in asset value to the building. At the same time, hotel operating expenses have been reduced by around USD $450,000 per year. Perhaps most strikingly, retrofitting the building to Passive House standard increased construction costs by only 2%. A large proportion of that uplift was offset through tax credits and utility company rebates, underlining an important point for developers: better buildings are not only more comfortable and lower carbon, but can also be highly attractive financially. “Passivhaus is value engineering!” was the key takeaway of Becker’s inspiring keynote presentation in the Passive House Network 2026 Conference.

HVAC & DHW Systems

The hotel’s heating and cooling are provided by a 3-pipe VRF system with heat recovery, allowing energy to be transferred efficiently across zones with different thermal demands. Ventilation is handled by Swegon energy recovery air handling units with heating and cooling coils. These units modulate the speed of the rotary wheel to recover more or less moisture depending on indoor and outdoor conditions, helping to maintain comfort while reducing energy demand. Domestic hot water is generated by air source heat pumps that charge two storage tanks in series, followed by a final ‘swing’ tank with an electric resistance heater for backup. According to the project team, those swing tank resistance heaters have never needed to come into operation—a telling indication of how effectively the system has been designed.

Control and Electrics

Hotel Marcel’s electrical and control strategy is every bit as forward-looking as its envelope and HVAC design. All LED lighting and internal blackout blinds operate on DC low-voltage power-over-ethernet (PoE) technology. This significantly reduces capital installation costs through fewer AC-to-DC drivers and less cabling, while also delivering operational savings of more than 30% compared with conventional lighting systems. In the guest rooms, the key card system is interfaced with the VRF heating and cooling controls, ensuring that air conditioning cannot be left running when the room is unoccupied. It is a simple but highly effective example of design, controls, and operations working together.

Solar PV & Battery Storage

The hotel’s renewable energy infrastructure is central to its net-zero ambition. Rooftop solar panels and parking-lot canopies together provide approximately 575,000 kWh of solar generation annually. Lithium-ion batteries provide 1.5 MWh of storage, and the site operates through a microgrid that allows the hotel to run in island mode, off the grid. This capacity for resilience, as well as decarbonisation, makes the project especially compelling in a hospitality context where uninterrupted service is essential.

Industrial Kitchen and Laundry Facilities

Behind the scenes, Hotel Marcel applies the same electrification logic to its operational spaces. The kitchen is fully electric, using induction cooking hobs and recirculation hoods that do not require venting to the outside or the conditioning of make-up air. The laundry facilities are also all electric, with heat pump clothes dryers that reduce peak electrical power demand from 128 kW to just 24 kW. The heat released in the laundry room is then absorbed by a heat pump water heater, which contributes to domestic hot water production. It is an elegant example of integrated systems thinking rather than isolated equipment decisions.

Lifts

Even the lifts contribute to the building’s performance strategy. KONE lifts generate power during braking, feeding recovered electricity back into the building’s systems. It is a relatively small measure in overall energy terms, but one that reflects the project’s broader attention to detail.

Food & Beverage

Sustainability at Hotel Marcel extends beyond the building systems into food and beverage operations. The hotel composts all food waste from the restaurant and catering, procures locally sourced ingredients and sustainably produced offerings, uses induction banquet equipment with no sterno usage, and opts for linenless tables in order to reduce the energy consumption associated with laundry. These choices show that environmental performance in hospitality depends as much on operational culture as on the building itself.

Recyclable & Healthy Products

The hotel’s approach to products and housekeeping is equally consistent. No single-use plastics are used for events, dining, or guest-room bathroom amenities. Environmentally friendly cleaning products are used throughout the building, and linens and towels are washed on request rather than nightly. These measures may sound simple, but together they reinforce the hotel’s wider commitment to healthier, lower-impact hospitality.

Service

What also stood out during my stay was the quality of service. The staff were warm, friendly, and clearly passionate about the hotel and the project as a whole. During the building tour, that pride was especially noticeable: they were enthusiastic in explaining what had been implemented, why it matters, and how the hotel operates differently from a conventional property. That human element—people who genuinely believe in the story they are telling—adds enormous value to the guest experience.

Hotel Marcel, New Haven

Certifications

Hotel Marcel’s performance has been recognised through an exceptional set of sustainability certifications. It has achieved LEED Platinum Certification, making it one of only 10 hotels in the United States to be certified LEED Platinum under the US Green Building Council’s standards, with points earned across categories such as water efficiency, energy efficiency, and integrated design process. It also holds Passive House Certification, making it the only Passive House-certified hotel in the US and the largest in the world, with a design that reduces energy use by as much as 80%. Net-zero certification is still pending, but the project is on track to become the nation’s first net-zero hotel through the elimination of fossil fuel usage.

Final Thoughts

Hotel Marcel is one of those rare buildings that succeeds on every level. Architecturally, it preserves and reinterprets a major piece of modernist heritage. Environmentally, it demonstrates that even difficult existing buildings can be transformed into high-performance assets. Commercially, it shows that Passive House can make sense in hospitality. And from the guest perspective, it is simply a very comfortable place to stay. Experiencing it during the Passive House Network USA’s 2026 Conference made that even clearer: the building was not just the venue, but part of the argument—living proof that the future of sustainable hospitality is already here.

Classroom overheating in Barcelona: HVAC simulation study

EnergyPlus simulation study on classroom overheating in Barcelona, thermal comfort, solar orientation and HVAC strategies for schools.

Classroom overheating in Barcelona: HVAC simulation study

Prevención del sobrecalentamiento en aulas: un estudio de simulación termodinámica en Barcelona
Plano aula

Introduction: why classroom overheating matters

As climate change intensifies summer heatwaves, preventing classroom overheating has become a critical design challenge for educational buildings in Mediterranean cities such as Barcelona. Schools must provide healthy, comfortable indoor conditions while also reducing energy consumption and operational complexity.

This article presents a thermodynamic building simulation study assessing overheating risk in two primary-school classrooms in Barcelona. The analysis uses DesignBuilder with the EnergyPlus calculation engine to evaluate whether a centralised 100% outdoor air HVAC system can maintain thermal comfort during school hours from May to September.

The study is relevant for architects, engineers, school operators and public authorities seeking evidence-based strategies for thermal comfort in schools, especially where cooling is delivered through a central air-handling unit rather than room-by-room terminal units.

* Schools shut in Spain from the end of June until September. However, for the simulations, July and August were included in the simulations, to have results under more challenging climate conditions. This was also done as the climate file is based on historical data. Currently, weather conditions that typically occurred in July now often occur in May.

Study objectives

The simulation was designed to answer three practical questions about classroom overheating, supply-air temperature and the impact of solar orientation.

  • How do east- and west-facing classrooms behave differently due to solar exposure, and what does this mean for HVAC control?
  • How many teaching hours exceed an operative temperature of 27°C despite cooled air being supplied at 14°C?
  • What relationship between outdoor temperature and supply-air temperature helps avoid both overheating and overcooling?

Simulation tools and building model

The dynamic simulation was carried out in DesignBuilder using the EnergyPlus engine. The model represents two identical classrooms located on the third floor of a primary school in Barcelona: one facing east and one facing west, with a north–south corridor between them.

The Barcelona–Airport IWEC II weather file developed by ASHRAE was used for the climate assumptions. July and August were included in the simulation period even though schools in Spain typically close during summer holidays, because these months provide a more demanding stress test for the system and help evaluate future climate resilience.

Internal floors and partitions were modelled as adiabatic. The envelope parameters comply with the minimum requirements of Spain’s CTE HE1 code for Climate Zone C. Windows are double glazed with Ug = 1.80 W/m²K, 79% visible transmittance and a solar factor of 59%. The external wall has U = 0.49 W/m²K, the roof has U = 0.40 W/m²K and air permeability is n50 = 3 ach.

Each classroom includes fixed external shading devices with a 50% reduction factor, representing expanded metal mesh shading. This shading reduces solar gains but does not eliminate the impact of orientation.

Internal loads and HVAC configuration

Each classroom has a floor area of 60 m² and is occupied by 31 pupils and one adult teacher during school hours. Lighting and equipment loads operate during teaching hours, Monday to Friday from 08:00 to 18:00, although lighting is assumed to be off during summer.

Ventilation is provided by a central air-handling unit supplying 100% outdoor air at 45 m³/h per person, equivalent to 1,395 m³/h per classroom. The system includes heat recovery with 79% sensible efficiency and 62% latent efficiency.

Cooling is provided by an air-to-water heat pump producing chilled water at 7°C for the AHU cooling coil. During summer school hours, the supply air temperature is assumed to be a constant 14°C at classroom supply level. In practice, duct heat gains and pressure losses may mean that the delivered supply air temperature and airflow differ from the simulation assumption. For May and September, a dual-setpoint control strategy is used to reduce overcooling: when outdoor temperature is below 16°C, supply air is delivered at 20°C; when outdoor temperature rises above 17°C, supply air is delivered at 14°C.

Internatl confort range

Thermal comfort criteria

Thermal comfort was assessed using operative temperature thresholds during school hours only. The comfort band was defined as 22°C to 27°C, with indoor relative humidity targets between 30% and 60% at 26°C. Conditions below 22°C were classified as too cold, while conditions above 27°C were classified as too hot.

Using operative temperature rather than air temperature alone provides a more representative assessment of how occupants experience the room, because it accounts for both air temperature and radiant temperature from surrounding surfaces.

Key results: overheating and overcooling risk

External Climate Overview (08:00–18:00, Mon–Fri)

The analysis shows that the central HVAC system generally maintains classroom comfort for most teaching hours. However, the results also demonstrate that orientation, solar gains and supply-air control are decisive factors in determining real comfort performance.

Key Results
Overheating Risk – Summary (% of teaching hours > 27 °C)

The east-facing classroom experiences the highest overheating risk, particularly in July and September, because morning solar gains coincide with early occupancy and rising outdoor temperatures. In July, the east classroom exceeds 27°C during approximately 7% of teaching hours despite the supply air being delivered at 14°C.

Overcooling Risk – Summary (% of teaching hours < 22 °C)

The west-facing classroom performs slightly better in terms of overheating, with only a small proportion of hours above 27°C in September. However, it is more exposed to overcooling in the morning during shoulder months, because delayed afternoon solar exposure does not compensate for early cool supply air.

This finding illustrates a common HVAC design challenge in schools: a single central control strategy can perform adequately on average while still creating different comfort outcomes across zones with different orientations.

Classroom overheating in Barcelona: HVAC study – Figure 9
Classroom overheating in Barcelona: HVAC study – Figure 10
Classroom overheating in Barcelona: HVAC study – Figure 11
Classroom overheating in Barcelona: HVAC study – Figure 12
Classroom overheating in Barcelona: HVAC study – Figure 13
Classroom overheating in Barcelona: HVAC study – Figure 14
Classroom overheating in Barcelona: HVAC study – Figure 15
Classroom overheating in Barcelona: HVAC study – Figure 16
Classroom overheating in Barcelona: HVAC study – Figure 17

Why orientation matters in classroom comfort

Solar orientation plays a significant role in overheating risk. East-facing classrooms receive direct solar radiation in the morning, when pupils arrive and classrooms are already occupied. This can quickly raise operative temperatures before the cooling system has fully compensated for the solar load.

West-facing classrooms receive more delayed solar radiation in the afternoon. This can reduce early-morning overheating risk but may create a different comfort profile later in the day. In the simulation, the west classroom was also more prone to mild overcooling during May and September.

For school buildings in Barcelona and other Mediterranean climates, façade orientation should therefore be considered alongside HVAC design. Identical classrooms can require different control strategies even when they have the same area, occupancy and envelope specification.

Recommended strategies to prevent classroom overheating

The simulation confirms that HVAC control is important, but it should be combined with passive design measures to create resilient school buildings. The most effective design approach is to reduce heat gains first, then use efficient mechanical systems to manage the remaining cooling load.

  • Improve external shading, especially on east and west façades where low-angle solar radiation is difficult to control.
  • Optimise glazing specifications, particularly solar factor, visible transmittance and frame performance.
  • Improve airtightness and insulation to reduce unwanted heat transfer and improve system predictability.
  • Reduce internal heat gains from lighting, equipment and operational schedules.
  • Consider night ventilation or free-cooling strategies where climate, acoustics and security conditions allow.
  • Commission airflow rates and supply-air temperatures carefully at classroom level rather than only at the AHU.

HVAC design lessons for schools

For 100% outdoor air systems serving multiple classrooms, ductwork design and commissioning are critical. Long duct runs can introduce pressure losses and heat gains, reducing airflow and increasing supply-air temperature at the classroom grilles. These effects can be especially important when the design relies on cool supply air to manage sensible loads.

The study also highlights the value of simple but intelligent control logic. A dual-setpoint strategy based on outdoor temperature can reduce overcooling in shoulder months without adding excessive complexity. However, zone-level monitoring or balancing may still be needed when classrooms have very different orientation or solar exposure.

Energy simulation with tools such as EnergyPlus and DesignBuilder allows design teams to test these strategies before construction or refurbishment. This supports better decisions, reduces performance gaps and helps align thermal comfort with energy-efficiency objectives.

Conclusions

The results show that a centralised 100% outdoor air HVAC system can generally maintain acceptable comfort in classrooms in Barcelona, but overheating risk is not eliminated. The east-facing classroom remains more vulnerable to overheating, especially in July, while the west-facing classroom shows a greater tendency toward mild overcooling during shoulder-season mornings.

Preventing classroom overheating requires a combined strategy: accurate energy simulation, façade-specific passive design, robust HVAC controls and careful commissioning. For Mediterranean school buildings facing warmer and more variable climate conditions, this integrated approach is essential for health, comfort, educational performance and energy efficiency.

FAQ: classroom overheating and thermal comfort

What causes classroom overheating?
Classroom overheating is caused by a combination of high outdoor temperatures, solar gains through windows, internal heat gains from pupils and equipment, insufficient shading and poorly matched HVAC control.

How can overheating in schools be prevented?
The most effective approach combines passive measures such as external shading, better glazing and reduced internal gains with HVAC strategies such as adaptive supply-air temperature control and careful commissioning.

What is a comfortable classroom temperature?
In this study, the comfort range was defined as an operative temperature between 22°C and 27°C during occupied school hours.

Why use EnergyPlus for school overheating studies?
EnergyPlus enables hourly dynamic simulation of weather, occupancy, solar gains, envelope performance and HVAC operation, making it suitable for evaluating overheating risk before decisions are implemented on site.

Can Naiades: first winter in our Passivhaus…warmth, comfort and tiny energy bills

First winter in our Passivhaus: The house has felt warm, calm and incredibly comfortable throughout the winter.

Can Naiades: first winter in our Passivhaus…warmth, comfort and tiny energy bills

By Oliver Style, Praxis CEO

I’ve lived in a few cool-temperate climates over the years – the UK, Switzerland, northern France – places where you’d expect winter to feel like winter. But, weirdly enough, I don’t think I’d ever really felt the cold at home as much as when I first moved to Barcelona in 2010 and installed myself in a flat in the historic city centre. Not because Barcelona is especially cold. It isn’t at all. But because many homes aren’t fit for the (thankfully!) short Mediterranean winter, and- in the case of the flat I moved in to- didn’t have the luxuries of central heating.

So, having got through our first summer in Can Naiades — our new Passivhaus — with flying colours, the next big question was: what would winter be like?

Would the house stay warm? Would the real energy consumption match the PHPP model? Would the solar PV and battery still pull their weight at the time of year when solar generation is at its lowest and energy demand is at its highest? Let’s have a look…

Can Naiades
Can Naiades

Nice and toasty

The short version is: it has been absolutely lovely.

The house has felt warm, calm and incredibly comfortable throughout the winter. Not “warm” in that slightly aggressive way you get when a radiator is blasting away in one corner of the room while your feet are still cold. Just evenly, quietly, consistently warm.

Temperatures have been stable and homogeneous throughout the house, with no noticeable cold spots, no draughts, and no cold air pouring in around windows, doors or junctions. That might sound like a small thing, but when you’ve lived in enough leaky buildings, the absence of discomfort becomes a kind of luxury.

There’s also something very particular about the quality of the air in a Passivhaus in winter. Because the house is airtight and ventilated continuously with heat recovery, we’re not relying on random infiltration through cracks and gaps to provide “fresh” air. The ventilation system just gets on with it: extracting stale, humid air from the kitchen and bathrooms, supplying filtered fresh air to the bedrooms, office and living spaces, and recovering heat from the outgoing air in the process.

The result is a house that feels fresh without feeling cold. That’s the magic trick. And then there’s the other great thing: no mould and no condensation. None. Zero.

This is the first home I’ve lived in, in Catalonia, where winter has not meant some combination of wet window frames, condensation on glass, suspiciously dark corners, or the occasional nasty surprise behind a wardrobe. In previous homes, condensation and mould felt like something you just had to manage: ventilate more, heat more, wipe it down, paint it over, move the furniture away from the wall, hope for the best.

Here, it just hasn’t happened. That’s not an accident. Warm internal surface temperatures, good insulation, reduced thermal bridges, airtightness, and continuous mechanical ventilation all work together. In practice, the experience is wonderfully uneventful: walls stay warm, indoor humidity is controlled, the air stays fresh, and nothing goes furry.

Fantastic!

The numbers

Of course, comfort is the most important thing. Buildings are for people, not spreadsheets. But the numbers matter too — especially if we want to show that low-energy, high-comfort buildings work not just in theory, but in real life, with real families, real weather, real cooking, real showers, real washing machines, and real life generally getting in the way.

So how did Can Naiades perform?

Really well. Over the winter period, the total measured energy consumption of the house was only 3% higher than the values predicted by the PHPP energy model. That’s a pretty remarkable result, given that PHPP is a design tool and real life is…well, real life, and consistently unpredictable.

There are always differences between modelling and measured performance: occupant behaviour, set-point temperatures, appliance use, hot water consumption, weather variations, commissioning, controls, and the million small things that happen once a building is occupied. So, to be within 3% of the predicted value is a very good sign that the design assumptions, construction quality and installed systems are all broadly doing what they were supposed to do.

Even better, despite winter being the worst time of year for solar generation — short days, lower sun angles, more cloud, and higher household demand — we were still 68% self-sufficient between November and February, using electricity generated by our solar PV panels and stored in the battery.

That really changes your relationship with energy. You become much more aware of when the sun is shining, when the battery is full, when it makes sense to run the washing machine, and how little energy the house actually needs to stay comfortable. It’s not about living with less comfort. It’s about getting more comfort from much less energy.

Compared with our previous flat, the difference is stark. This winter, we spent 79% less on energy bills and used 93% less energy.

Ninety-three percent less energy!

That number still makes me stop and look at it twice. Because this isn’t a smaller, colder, more miserable house. It’s the opposite: it’s bigger, warmer, healthier, quieter and more comfortable. We’re not saving energy by putting up with discomfort. We’re saving energy because the building fabric does most of the work before the mechanical systems even need to get involved.

That, for me, is the key point.

The house doesn’t need much heating because it doesn’t lose much heat and because the sun does most of the heating. The windows don’t feel cold because they’re high-performance and properly installed. The air doesn’t feel stale because the ventilation system is doing its job. The indoor temperature doesn’t swing all over the place because the envelope is insulated, airtight and carefully designed. The systems can be small because the demand is small.

It’s all very boring, really. And that’s exactly how it should be.

Can Naiades: First Winter PHPP vs. measured energy comsumption
Can Naiades: First Winter. Measured solar PV production
Can Naiades: First Winter. Real solor PV generation vs. real energy consumption

The best kWh…

After our first summer, I wrote that living in a Passivhaus in a Mediterranean heat wave felt like a dream come true. After our first winter, I’d say the same thing again — only with a jumper I didn’t really need.

Can Naiades has been warm, fresh, dry and comfortable, while using a tiny amount of energy. The PHPP model has proven to be very close to measured reality. The PV and battery have provided a surprisingly high level of self-sufficiency, even in winter. And our energy bills have dropped dramatically compared with our previous home.

But beyond the technical satisfaction, there’s a broader reflection.

We often talk about energy in terms of production: more renewables, more generation, more infrastructure, more supply. And of course, we need all of that. But living in this house is a daily reminder that the best kWh is still the one you don’t consume.

That truth resonates every time another war breaks out, another geopolitical crisis sends energy prices sky high, or another family has to choose between heating their home properly and paying the rest of the bills.

Reducing demand is not boring. It’s resilience. It’s comfort. It’s climate action. It’s protection against volatile energy prices. And, at the most basic level, it means living in a home that feels good.

After one summer and one winter in Can Naiades, I can confirm: Passivhaus works. And it works beautifully.

Check out our previous articles about the project:

Thank you to the following people and companies for their support:

Passivhaus Homes in Tordera: BYKO completes the Guifré el Pilós development certified by Praxis

Meta description: BYKO delivers three Passivhaus homes in Tordera certified by Praxis: Zehnder heat recovery ventilation, aerothermal DHW, ETICS and 2D timber modules.

Passivhaus Homes in Tordera: BYKO completes the Guifré el Pilós development certified by Praxis

Viviendas Passivhaus en Tordera: BYKO culmina la promoción Guifré el Pilós certificada por Praxis

In Tordera (Barcelona), BYKO has completed the Guifré el Pilós development: a set of three terraced homes designed and built to meet the Passivhaus – Low Energy Building standard, with certification carried out by Praxis Resilient Buildings. The project was developed in collaboration with La Llotja Arquitectes and is located in Tordera, province of Barcelona, Catalonia, Spain.

Architecture

Each home is arranged over two floors with a treated floor area close to 100 m² and a highly functional layout: open‑plan kitchen-living‑dining room, and a full bathroom on the ground floor; and on the first floor: two single bedrooms, a master bedroom with en‑suite, an additional bathroom, a utility/plant room and a study area. Private front and rear patios complete the programme.

Construction system, structure and 2D prefabrication

The construction system uses 2D industrialised lightweight timber‑frame modules for walls and roof, reducing on‑site time and ensuring precision—key to achieving Passivhaus‑level of air‑tightness and thermal‑bridge control. Modules were delivered with the air‑tight layer (FINSA Superpan timber particle board) and external thermal insulation (pre‑render) already installed. Windows are PVC with triple low‑e, solar‑control glazing, and motorised shutters for summer shading.

Building services, ventilation and indoor air quality

  • Balanced mechanical ventilation with heat and moisture recovery (Zehnder Climos 200) for continuous fresh air, minimal thermal loss and effective particle filtration.
  • Space conditioning via air‑to‑air heat pump with ducted indoor units, sized for the building’s low heating and cooling loads.
  • Domestic hot water via an air-to-water heat pump hot water unit with a 190‑L tank; seasonal efficiency for DHW of SCOP = 3.52.
  • Loxone monitoring and controls (ventilation, HVAC, DHW and general electricity) for optimisation and maintenance.
  • Optional rooftop PV to further improve the energy balance.

Passive design, air‑tightness and thermal bridges

As part of the Passivhaus certification, Praxis verified air‑tightness (n₅₀) via blower‑door testing, the elimination of thermal bridges at envelope junctions and openings, active solar protection with motorised shutters, and proper commissioning of the MVHR system. These measures cut heating and cooling demand and deliver 24/7 comfort with very low energy use.

360º comfort

  • Homogeneous indoor temperatures without drafts or noticeable stratification.
  • Consistently healthy indoor air quality thanks to MVHR with filtration (CO₂ and VOCs kept in check).
  • Low noise levels due to the high‑performance envelope and windows.

Voices from the project

“With Guifré el Pilós we reaffirm our commitment to ultra‑low‑energy, high‑comfort homes, bringing the Passivhaus standard to families who value quality, health and efficiency,” says Ismael Fernández, developer and builder at BYKO.

“Passivhaus certification rigorously validates real‑world building performance. At Guifré el Pilós, we paid careful attention to air‑tightness, thermal‑bridge control, high‑efficiency ventilation and summer performance, to ensure year‑round comfort,” says Oliver Style, Passivhaus certifier at Praxis Resilient Buildings.