Glaser vs WUFI: Comparative Hygrothermal Analysis of Interior Insulation on Solid Brick Walls in Two Climates
We know that a deep energy retrofits can be delicate, so the question often arises: what tools can I use for the hygrothermal analysis of potential moisture damage?
Glaser vs WUFI: Comparative Hygrothermal Analysis of Interior Insulation on Solid Brick Walls in Two Climates
We know that a deep energy retrofits can be delicate, so the question often arises: what tools can I use for the hygrothermal analysis of potential moisture damage?

In this article, we present a comparison between the simplified Glaser calculation method, as specified in ISO 13788 [1], and dynamic hygrothermal simulation with WUFI Pro 1D [2], in accordance with EN 15026 [3], in two Spanish climates: Barcelona and Burgos. The case study looks at a historic solid brick wall, unrendered, with interior insulation, where we analyse the relative humidity on the interior face of the existing wall, and compare the results from each calculation method. Although ISO 13788 makes clear what the limitations of the Glaser method are, and that it should not be used in cases like this, in practice it is still widely used among building professionals. The results underline the limitations of the simplified method for analysing moisture transport in solid walls with interior insulation.
Introduction
A whole‑building deep energy retrofit radically changes the hygrothermal response of the building envelope. What if I can only install interior insulation on a solid brick wall, exposed to driving rain? Will there be condensation and moisture problems? What tools can I use to analyse the risk? One of the most common tools is the Glaser method, included in ISO 13788. But how reliable are its results?
Let’s look at the results of a comparative study between the Glaser method and a dynamic hygrothermal simulation with WUFI Pro 1D, for a solid brick wall with interior insulation, in the climates of Burgos and Barcelona, Spain.

What tools can I use for a hygrothermal risk analysis of moisture damage in retrofit projects?
The best‑known calculation method is Glaser, covered by ISO 13788 and developed in 1958 for analysing lightweight assemblies. It is a simplified calculation method, based on monthly average indoor and outdoor temperatures and relative humidity. It assumes:
- Steady‑state heat transfer
- Moisture transfer only by vapor diffusion
- Materials are completely dry at the start
The calculation determines whether there are critical points of condensation over one year, neglecting the following physical processes:
- Variation of hygrothermal properties of materials due to their moisture content
- Latent heat absorption and release
- Capillary suction and liquid transport within materials
- Airflow through the building element
- The hygroscopic capacity of materials
ISO 13788 states that the method is valid only for building elements where these effects are negligible. So it shouldn’t be used to analyse massive assemblies with interior or exterior insulation, or for elements exposed to rain or subject to freeze–thaw cycles. Spain’s CTE DB‑HE building regulations also explicitly states this premise. Nevertheless, the Glaser method is often used incorrectly in practice.
By contrast, dynamic hygrothermal calculation via numerical simulation—described in EN 15026 and implemented in tools like WUFI and Delphin—addresses Glaser’s limitations through an hourly numerical analysis that considers all the above physical processes, realistic boundary conditions, and initial moisture conditions in materials, reflecting real‑world scenarios in retrofit or new construction.
Comparison: Glaser vs. WUFI — Solid Brick Wall with Interior Insulation
Below are the results of a comparative study between Glaser and WUFI, for the climates of Barcelona and Burgos. A 5‑cm interior thermal insulation layer is applied. A second variant with a vapor barrier on the warm side of the insulation is also studied.
The brick wall is 29 cm thick. Of the 29 cm, 80% is brick and 20% is lime mortar. The one‑dimensional section is subdivided to reflect this brick‑mortar ratio, according to the data in Figure 2, following the methodology of Little et al. [4]. Simulations in WUFI were initialized with materials at a moisture content corresponding to 80% RH, at 20°C. Simulations were run for 10 years, starting in October. The WUFI results presented in the comparison with Glaser correspond to year 10. The wall orientation in the WUFI calculations is north, with a rainwater penetration coefficient of 70%. Basic hygrothermal properties of the sample materials are shown in Figure 2.

To compare WUFI results with the monthly Glaser method (whose results do not have an hourly resolution), monthly average values of temperature and relative humidity were extracted from the hourly WUFI outputs.
Results
Figure 3 shows the results for the Barcelona climate with 5 cm of interior insulation. In January, Glaser yields temperatures 16% higher than the dynamic calculation and relative humidity 14% lower.

Figure 4 shows the results for the Burgos climate. In January, Glaser yields temperatures 22% higher than the dynamic WUFI calculation and relative humidity 4% lower.

Figure 5 shows the results for Barcelona with a vapor barrier installed between the interior insulation and the gypsum plasterboard. In January, Glaser yields temperatures 16% higher than the dynamic WUFI calculation and relative humidity 81% lower. The Glaser method indicates no risk of moisture damage, with a maximum RH of 67%, whereas WUFI indicates a mean RH of 99%, implying risk of moisture‑related pathologies.

Figure 6 shows the results for the Burgos climate. The trend is identical: the Glaser results yield much lower relative humidity values than the dynamic calculation with WUFI.

Conclusions
In Barcelona without a vapor barrier, the relative humidity results on the interior face of the existing wall are 2% to 28% lower with the Glaser method than the dynamic WUFI results. In Burgos, the difference ranges between 2% higher and 26% lower.
For the wall with a vapor barrier, the difference is much more pronounced: from 48% to 81% lower in Barcelona, and from 62% to 116% in Burgos.
The results indicate that the Glaser method described in UNE‑ISO 13788 is not suitable for analysing moisture transfer in unrendered solid walls exposed to rain with interior insulation. The large discrepancy between the results may lead to incorrect hygrothermal design and potential interstitial moisture damage.
For situations like this, that are hygrothermally sensitive, we recommend carrying out a dynamic calculation and/or consulting a specialist. We also recommend extending the study to analyse the water content of materials and the effect of air infiltration/exfiltration (beyond an analysis of relative humidity on the interior face of the wall). In addition, we recommend in‑situ testing to determine the liquid transport coefficient of a historic solid brick wall, since its hygrothermal behaviour can vary widely.
References
[1] EN ISO 13788:2016. Hygrothermal performance of building components and building elements — Internal surface temperature to avoid critical surface humidity and interstitial condensation — Calculation methods (ISO 13788:2012).
[2] WUFI (Wärme Und Feuchte Instationär): dynamic hygrothermal simulation software for analysing heat and moisture transport in building components, developed by the Fraunhofer Institute, Germany.
[3] EN 15026:2007. Hygrothermal performance of building components and building elements — Assessment of moisture transfer by numerical simulation.
[4] Joseph Little, Carolina Ferraro & Beñat Arregi (2015). Assessing risks in insulation retrofits using hygrothermal software tools. Heat and moisture transport in internally insulated stone walls. Historic Environment Scotland Technical Paper 15, Second Edition, 2015, Edinburgh, Scotland.
[5] ASHRAE 160‑2016. Standard 160‑2016 — Criteria for Moisture‑Control Design Analysis in Buildings (ANSI Approved).










































































































